3RW3036-1BB14 SIEMENS, 3RW3036-1BB14 Datasheet - Page 18

SIRIUS SOFTSTARTER, S2, 45A, 22KW/400V

3RW3036-1BB14

Manufacturer Part Number
3RW3036-1BB14
Description
SIRIUS SOFTSTARTER, S2, 45A, 22KW/400V
Manufacturer
SIEMENS
Datasheet

Specifications of 3RW3036-1BB14

Supply Voltage Range
200Vac To 480Vac
No. Of Phases
Three
Power Rating
22kW
Current Rating
45A
Operating Temperature Range
-25°C To +60°C
Approval Bodies
CE, IEC, UL, CSA
Control Voltage
RoHS Compliant
3RW30
for standard applications
Function
The space required by the compact SIRIUS 3RW30 soft starter
is often only about one third of that required by a wye-delta
assembly of comparable rating. This not only saves space in the
control cabinet and on the standard mounting rail but also does
away completely with the wiring work needed for wye-delta
starters. This is notable in particular for higher motor ratings
which are only rarely available as fully wired solutions.
At the same time the number of cables from the starter to the
motor is reduced from six to three. Compact dimensions, short
start-up times, easy wiring and fast commissioning make
themselves felt as clear-cut cost advantages.
The bypass contacts of these soft starters are protected during
operation by an integrated solid-state arc quenching system.
This prevents damage to the bypass contacts in the event of a
fault, e.g. brief disconnection of the control voltage, mechanical
shocks or life-related component defects on the coil operating
mechanism or main contact spring.
The new series of devices comes with the "polarity balancing"
control method, which is designed to prevent direct current
components in two-phase controlled soft starters. On two-phase
controlled soft starters the current resulting from superimposition
of the two controlled phases flows in the uncontrolled phase.
This results for physical reasons in an asymmetric distribution of
the three phase currents during the motor ramp-up. This
phenomenon cannot be influenced, but in most applications it is
non-critical.
Controlling the power semiconductors results not only in this
asymmetry, however, but also in the previously mentioned direct
current components which can cause severe noise generation
on the motor at starting voltages of less than 50 %. The control
method used for these soft starters eliminates these direct
current components during the ramp-up phase and prevents the
braking torque which they can cause.
Technical specifications
Type
Rated values
Rated control supply voltage
• Tolerance
Rated control supply current
• STANDBY
• During pick-up
• ON
Rated frequency
• Tolerance
Control input
IN
Power consumption with version
• 24 V DC
• 110/230 V AC
Relay outputs
Output 1
Rated operational current
Protection against overvoltages
Short-circuit protection
Operating indications
Off
Start
Bypass
Error signals
• 24 V DC:
• 110 ... 230 V AC: U < 0.75 x U
Electrical overloading of bypass
(reset by removing IN command)
Missing mains voltage, phase failure, missing load
Device fault
Control electronics
6/12
3RW Soft Starters
Siemens LV 1 N SIRIUS Soft Starters · 01/2008
U < 0.75 x U
s
s
or U > 1.25 x U
or U > 1.15 x U
s
s
ON
Terminal
13/14
A1/A2
© Siemens AG 2008
V
%
mA
mA
mA
Hz
%
mA
mA
A
A
LED
3RW30 1. , 3RW30 2.
24
±20
< 50
< 100
< 100
50/60
±10
ON/OFF
approx. 12
AC: 3/6; DC: 1.5/3
Operating indication (NO)
3 AC-15/AC-14 at 230 V,
1 DC-13 at 24 V
Protection by means of varistor through contact
4 A gL/gG operational class;
6 A quick (fuse is not included in scope of supply)
DEVICE
Green
Green
Green
Off
Off
Yellow
Green
Red
It creates a motor ramp-up that is uniform in speed, torque and
current rise, thus permitting a particularly gentle, two-phase
starting of the motors. At the same time the acoustic quality of
the starting operation comes close to the quality of a three-
phase controlled soft starter. This is made possible by the on-
going dynamic harmonizing and balancing of current half-waves
of different polarity during the motor ramp-up. Hence the name
"polarity balancing".
• Soft starting with voltage ramp; the starting voltage setting
• Integrated bypass contact system to minimize power loss
• Setting with two potentiometers
• Simple mounting and start-up
• Mains voltages at 50/60 Hz, 200 to 480 V
• Two control voltage versions 24 V AC/DC and 110 to 230 V AC/DC
• Wide temperature range from -25 °C to +60 °C
• The built-in auxiliary contact ensures user-friendly control and
range U
from 0 s to 20 s.
possible further processing within the system
graphs see page
s
is 40 % to 100 % and the ramp time t
110 ... 230
-15/+10
15
15
STATE/BYPASSED/
FAILURE
Off
Green flashing
Green
Red
Red
Red
Red
Red
6
6/22).
3RW30 3., 3RW30 4.
24
±20
< 4000
DEVICE
Green
Green
Green
Off
Off
--
Green
Red
20
20
110 ... 230
-15/+10
< 50
< 500
< 50
STATE/BYPASSED/
FAILURE
Off
Green flashing
Green
Red
Red
--
Red
Red
(for status
R
can be set