SNAP-AIPM OPTO 22, SNAP-AIPM Datasheet

Power Monitoring Module

SNAP-AIPM

Manufacturer Part Number
SNAP-AIPM
Description
Power Monitoring Module
Manufacturer
OPTO 22
Type
Inputr
Datasheets

Specifications of SNAP-AIPM

Accessory Type
Single-phase Power Monitoring Module
Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Signal Input Type
85 To 250V And 0 To 10A RMS
Brand/series
SNAP Series
Connection To Host
Backplane
Current, Input
100 mA
Current, Supply
0 to 10 A
Dimensions
82.55mmL×18.29mmW×90.17mmH
Input
85 to 250/0 to 10 VAC/AAC
Input Resolution
10 mV
Input Type
Analog
Input, Range
85 to 250/0 to 10 VAC/AAC
Mounting Type
PCB
Number Of Channels
2
Number Of Inputs
2 Channels
Primary Type
Control
Resistance, Input
1 Megohms
Special Features
Transformer Isolation, Optical Isolation
Standards
UL, CSA, CE Certified
Temperature, Operating
0 to +70 °C
Voltage, Isolation
4000 V
Voltage, Supply
5 VDC
No. Of Analog Inputs
4
Resolution
10mV, 400uA
Rohs Compliant
No
For Use With
Snap I/O Modules
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
SNAP Power Monitoring
Modules
Description
SNAP power-monitoring analog input modules provide an
efficient way to monitor AC voltage and current using a SNAP
PAC rack-mounted controller or SNAP PAC brain. These
modules can be used with both standard wired SNAP PAC
brains and controllers and Wired+Wireless
Three power-monitoring modules are available:
• The SNAP-AIPM monitors single-phase AC power.
• The SNAP-AIPM-3 monitors three-phase AC power using
• The SNAP-AIPM-3V monitors three-phase AC power using
All modules mount on a SNAP PAC rack right alongside digital,
analog, and serial SNAP I/O
SNAP power-monitoring modules help you measure and
control power usage, so you can reduce costs, maintain power
quality, and track energy use. If they are part of a SNAP PAC
System running a PAC Control
automatically perform additional calculations and respond to
any problems the module reports.
© 2006–2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.
Power Monitoring Modules
Wired inputs:
- Volts
- Amps (or
volts from
0.333 VAC CT)
Features
a standard current transformer (CT).
a 0.333 VAC current transformer (CT).
Convenient pluggable wiring
Single-phase or three-phase power monitoring
Monitors AC RMS voltage and AC RMS current;
calculates true power and volt-amps
10% over range
25,000 counts of resolution over input ranges
Out-of-range indication
Factory calibrated; no user adjustment necessary
SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com
modules.
strategy, strategy logic can
Data you get:
- Volts
- Amps
- Watts
- Volt Amps
And in SNAP-AIPM-3
and SNAP-AIPM-3V:
- True Power sum ABC
- True Power absolute
value sum
models.
SNAP racks use a retention rail locking system that holds
modules securely to the rack. Normally, a hold-down screw is
not required. However, for applications that require additional
module security, each module has provisions for two 4-40 by
½-inch standard machine screws to hold each module in
position on the SNAP rack.
SNAP-AIPM
The SNAP-AIPM individually and simultaneously measures
single-phase AC volts RMS and amps RMS and calculates true
power and volt-amps. Power factor can then be calculated
from true power and volt-amp values. Because true power is a
signed value, either leading or lagging power factor can be
calculated.
The SNAP-AIPM module is designed for 85–250 volts and
0–10 amps, but it can also monitor AC line currents greater
than 10 amps using a standard current transformer (CT) of
suitable ratio. For line voltage larger than 250 VAC, use a step-
down potential transformer. If hazardous voltage or current is
to be monitored, an interposing potential transformer and a
CT must be used for safety.
Part Number
SNAP-AIPM
SNAP-AIPM-3
SNAP-AIPM-3V
Part
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com
SNAP-AIPM Module
Single-phase Power Monitoring Module,
85–250 V RMS and 0–10 A RMS Inputs
Three-phase Power Monitoring Module,
85–300 V RMS and 0–5 A RMS Inputs for
Each Phase
Three-phase Power Monitoring Module,
85–300 V RMS and 0–0.333 VAC CT
Inputs for Each Phase
Description
PAGE
1

Related parts for SNAP-AIPM

SNAP-AIPM Summary of contents

Page 1

... Because true power is a signed value, either leading or lagging power factor can be calculated. The SNAP-AIPM module is designed for 85–250 volts and 0–10 amps, but it can also monitor AC line currents greater than 10 amps using a standard current transformer (CT) of suitable ratio ...

Page 2

... For each of the three phases, the module includes the same four channels as in the SNAP-AIPM (see previous page); in addition, it includes two summation values. Calculations occur within the module and are available to the SNAP PAC brain or rack- mounted controller ...

Page 3

... SNAP Power Monitoring Modules Note for legacy hardware: The SNAP-AIPM module can also be used with SNAP Ultimate, SNAP Ethernet, and SNAP Simple brains and on a SNAP M-series or B-series mounting rack. Specifications: SNAP-AIPM Voltage Inputs (each voltage channel) Recommended Input Range 85 to 250 VAC RMS ...

Page 4

... Ambient Temperature: Operating Storage Agency Approvals Warranty Calculated Outputs True Power Volt Amps Specifications: SNAP-AIPM-3 and SNAP-AIPM-3V Voltage Inputs (each voltage channel) Recommended Input Range 85 to 300 VAC RMS* Scaled Input Range 0 to 300 VAC RMS Input Over Range To 330 volts ...

Page 5

... Energy Sum value of each A, B, and C, always positive) *Inputs on older modules were 0–250 V and for SNAP-AIPM-3, 0–10 A. Before wiring or scaling, check printed information on the module to make sure you are using the correct voltage and current. Contact Opto 22 Product Support with any questions. ...

Page 6

... CT and module. IMPORTANT: For all installations 300 VAC (or 85–250 for the SNAP-AIPM), both Actual and Scaled Volts (point 0 on all modules, plus points 4 and 8 on the SNAP-AIPM-3 and SNAP-AIPM-3V) should remain at the default: 0–250 VAC for the SNAP-AIPM and 0– ...

Page 7

... SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com © 2006–2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations. Scaling Example 2: SNAP-AIPM with PT For line voltage higher than 250 VAC, a step-down potential transformer (PT) must be used ...

Page 8

... Scaling Example 3: SNAP-AIPM-3 without PT Leave Actual values at their defaults for all points, and leave Lower Scaled values at 0. Calculate Upper Scaled values for points as follows: 1 Points Always 300 volts and 300 VAC. (For line voltage over 300 V, use Example 2.) Points (CT primary / CT secondary) Points 2, 6, 10: Upper Scaled for voltage * Upper Scaled for current (ex ...

Page 9

... Scaling Example 6: SNAP-AIPM-3V with PT For line voltage higher than 300 VAC Split-Core potential transformer (PT) must be used. The SNAP-AIPM-3V requires CTs with a 0.333 VAC secondary. Leave Actual values at their defaults for all points, and leave Lower Scaled at 0. Calculate Upper Scaled as follows: Points 300 * PT ratio ...

Page 10

... Use conservative wire gauges with proper voltage ratings. CAUTION: Terminals and 6 share a common connection inside the module. CAUTION: The SNAP-AIPM module does not contain a fuse. Protect the system by adding a fuse. See below for a suggested vendor. Suggested vendors Protection fuses: http://www.littelfuse.com Voltage and current transformers: http://www ...

Page 11

... See cautions on page 10. If you have a SNAP-AIPM-3 module, see SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com © 2006–2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations. ...

Page 12

... Three-Phase Wiring to Two SNAP-AIPM Modules See cautions on page 10. If you have a SNAP-AIPM-3 module, see Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com PAGE SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com 12 © ...

Page 13

... Individual phase power • Individual phase volt-amps IMPORTANT—Voltage change: Older SNAP-AIPM-3 modules used 0–250 volts and 0–10 amps. Before wiring or scaling, check the printed information on the module to make sure you are using the correct voltage and current. ...

Page 14

... Volts, phase A to phase C • Volts, phase B to phase C IMPORTANT—Voltage change: Older SNAP-AIPM-3 modules used 0–250 volts and 0–10 amps. Before wiring or scaling, check the printed information on the module to make sure you are using the correct voltage and current. ...

Page 15

... Individual phase power • Individual phase volt-amps Suitable current transformers (CTs) for use with the SNAP-AIPM-3V are available from Opto 22. See form #1938, the Split-Core Current Transformers Data SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com © ...

Page 16

... Using this wiring, after you scale the module, the following measurements are available. All measurements are synchronously updated every second: • Volts, phase A to phase C • Volts, phase B to phase C Suitable current transformers (CTs) for use with the SNAP-AIPM-3V are available from Opto 22. See form #1938, the Split-Core Current Transformers Data information. ...

Page 17

... SNAP Power Monitoring Modules Dimensional Drawing—SNAP-AIPM SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com © 2006–2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations. ...

Page 18

... Dimensional Drawing—SNAP-AIPM-3 and SNAP-AIPM-3V Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com PAGE SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com 18 © 2006–2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations. ...

Page 19

... SNAP Power Monitoring Modules Dimensional Drawing—All AIPM Modules IMPORTANT: The mounting rack connector has 24 pins; the module connector has 20 pins. The extra pins on the mounting rack connector prevent misalignment of the module during installation. SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com © ...

Page 20

... Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations. SNAP Power Monitoring Modules NOTE: The SNAP-AIPM-3 and SNAP-AIPM-3V have three connectors on the top of the case, at the same height as shown below. ...

Page 21

... SNAP I/O I/O provides the local connection to sensors and equipment. Opto 22 SNAP I/O offers points of reliable I/O per module, depending on the type of module and your needs. Analog, digital, serial, and special-purpose modules are all mixed on the same mounting rack and controlled by the same processor (SNAP PAC brain or rack-mounted controller) ...