SNAP-AIPM OPTO 22, SNAP-AIPM Datasheet
SNAP-AIPM
Specifications of SNAP-AIPM
Related parts for SNAP-AIPM
SNAP-AIPM Summary of contents
Page 1
... Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations. SNAP-AIPM Module The SNAP-AIPM module is designed for 85–250 volts and 0– 10 amps, but it can also monitor AC line currents greater than 10 amps using a standard 5-Amp current transformer (CT) of suitable ratio ...
Page 2
... For each of the three phases, the module includes the same four channels as in the SNAP-AIPM (see previous page); in addition, it includes two summation values. Calculations occur within the module and are available to the SNAP PAC brain or rack- mounted controller ...
Page 3
... SNAP-AIPM Modules Note for legacy hardware: The SNAP-AIPM module can also be used with SNAP Ultimate, SNAP Ethernet, and SNAP Simple brains and on a SNAP M-series or B-series mounting rack. Specifications: SNAP-AIPM Voltage Inputs (each voltage channel) Recommended Input Range 85 to 250 VAC RMS ...
Page 4
... Ambient Temperature: Operating Storage Agency Approvals Warranty Calculated Outputs True Power Volt Amps Specifications: SNAP-AIPM-3 and SNAP-AIPM-3V Voltage Inputs (each voltage channel) Recommended Input Range 85 to 250 VAC RMS Scaled Input Range 0 to 250 VAC RMS Input Over Range To 275 volts ...
Page 5
... Wiring should be done by a licensed electrician. Be sure to use appropriate CTs, and never mix CT types on the same device. The wrong CT can cause severe damage to equipment. For the SNAP-AIPM-3V module, suitable CTs with a 0.333 VAC secondary are available from Opto 22. See form #1938, the Split-Core Current Transformers Data Sheet, for more information ...
Page 6
... Click the plus sign next to the module to open its points. For the SNAP-AIPM, you see four points. For the SNAP-AIPM-3 (shown above) or the SNAP-AIPM-3V, you see 14. You must configure each point. Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com ...
Page 7
... Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations. Scaling Example 2: SNAP-AIPM or SNAP-AIPM-3 with PT For line voltage higher than 250 VAC, a step-down potential transformer (PT) must be used ...
Page 8
... Scaling Example 3: SNAP-AIPM-3V without PT The SNAP-AIPM-3V requires CTs with a 0.333 VAC secondary. (For suitable CTs, see Opto 22 form #1938, the Current Transformers Data Sheet.) Leave Actual values at their defaults for all points, and leave Lower Scaled at 0. Calculate Upper Scaled as follows: Points Always 250 volts for line voltage between 85 and 250 VAC ...
Page 9
... Use conservative wire gauges with proper voltage ratings. CAUTION: Terminals and 6 share a common connection inside the module. CAUTION: The SNAP-AIPM module does not contain a fuse. Protect the system by adding a fuse. See below for a suggested vendor. Suggested vendors Protection fuses: http://www.littelfuse.com Voltage and current transformers: http://www ...
Page 10
... Wiring Diagrams—SNAP-AIPM (continued) Three-Phase Wiring to Three SNAP-AIPM Modules See cautions on page 9. If you have a SNAP-AIPM-3 module, see Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com PAGE 10 © 2006–2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations. ...
Page 11
... Three-Phase Wiring to Two SNAP-AIPM Modules See cautions on page 9. If you have a SNAP-AIPM-3 module, see © 2006–2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations. page 13 ...
Page 12
... Wiring Diagrams—SNAP-AIPM-3 Three-Phase Wiring to SNAP-AIPM-3 Module CAUTION: Be very careful when connecting input channels. Do not connect line voltage to the current input channel; such a connection will cause severe damage to the module. This damage is not covered by warranty. Use a current transformer instead. CAUTION: Use caution when selecting wire gauges for your application ...
Page 13
... SNAP-AIPM Modules Wiring Diagrams—SNAP-AIPM-3 Three-Phase Wiring to SNAP-AIPM-3 Module NOTE: This wiring method is less expensive than the one on page 12 but does not provide as much information. CAUTION: Be very careful when connecting input channels. Do not connect line voltage to the current input channel; such a connection will result in severe damage to the module ...
Page 14
... Individual phase and load current • Individual phase power • Individual phase volt-amps Suitable current transformers (CTs) for use with the SNAP-AIPM-3V are available from Opto 22. See form #1938, the Split-Core Current Transformers Data Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com ...
Page 15
... Volts, phase B to phase C • 3-phase sum of 1 sec.—unsigned energy (watt secs) Suitable current transformers (CTs) for use with the SNAP-AIPM-3V are available from Split-Core Current Transformers Data Opto 22. See form #1938, the information. © ...
Page 16
... Dimensional Drawing—SNAP-AIPM Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com PAGE 16 © 2006–2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations. SNAP-AIPM Modules ...
Page 17
... SNAP-AIPM Modules Dimensional Drawing—SNAP-AIPM-3 and SNAP-AIPM-3V © 2006–2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations. Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com ...
Page 18
... Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations. IMPORTANT: The mounting rack connector has 24 pins; the module connector has 20 pins. The extra pins on the mounting rack connector prevent misalignment of the module during installation. SNAP-AIPM Modules ...
Page 19
... Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations. NOTE: The SNAP-AIPM-3 ans SNAP-AIPM-3V have three connectors on the top of the case, at the same height as shown below. Opto 22 • ...
Page 20
... SNAP I/O I/O provides the local connection to sensors and equipment. Opto 22 SNAP I/O offers points of reliable I/O per module, depending on the type of module and your needs. Analog, digital, serial, and special-purpose modules are all mixed on the same mounting rack and controlled by the same processor (SNAP PAC brain or rack-mounted controller) ...