CS1W-CN713 Omron, CS1W-CN713 Datasheet - Page 68

no-image

CS1W-CN713

Manufacturer Part Number
CS1W-CN713
Description
"CABLE CS1 EXP I/O,70cm"
Manufacturer
Omron
Datasheet

Specifications of CS1W-CN713

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Memory Area Structure
46
Unit Specifications
IR area
(note 1)
Controller Link
status areas
MACRO
operand
area
(note 2)
Inner Board slot 1
area
Analog settings
area (note 1)
High-speed
Counter 0 PV
(note 1)
Inner Board slot 2
area
SR area
HR area
Data area
Input
area
Output
area
Work
areas
Input
area
Output
area
256
bits
256
bits
2,528
bits
min.
(note
2)
96 bits
96 bits
64 bits
64 bits
256
bits
64 bits
32 bits
192
bits
184
bits
1,600
bits
Size
IR 090 to IR 095
IR 190 to IR 195
IR 096 to IR 099
IR 196 to IR 199
IR 000 to IR 015
IR 100 to IR 115
IR 016 to IR 089
IR 116 to IR 189
IR 216 to IR 219
IR 224 to IR 229
IR 200 to IR 215
IR 220 to IR 223
IR 230 to IR 231
IR 232 to IR 243
SR 244 to
SR 255
HR 00 to HR 99
Words
IR 00000 to IR 01515
IR 10000 to IR 11515
IR 01600 to IR 08915
IR 11600 to IR 18915
IR 21600 to IR 21915
IR 22400 to IR 22915
IR 09000 to IR 09515
IR 19000 to IR 19515
IR 09600 to IR 09915
IR 19600 to IR 19915
IR 20000 to IR 21515
IR 22000 to IR 22315
IR 23000 to IR 23115
IR 23200 to IR 24315
SR 24400 to
SR 25515
HR 0000 to HR 9915
Bits
Input bits can be allocated to Input Units or I/O
Units. The 16 bits in IR 000 are always allocated
to the CPU Unit’s built-in inputs.
Output bits can be allocated to Output Units or
I/O Units.
Work bits do not have any specific function and
they can be freely used within the program.
Used to indicate the Controller Link data link
status information. (Can be used as work bits
when a Controller Link Unit is not connected.)
Used to indicate the Controller Link error and
network participation information. (Can be used
as work bits when a Controller Link Unit is not
connected.)
Used when the MACRO instruction, MCRO(99),
is used. (Can be used as work bits when the
MACRO instruction is not used.)
These bits are allocated to the Inner Board
mounted in slot 1 of a CQM1H-CPU51/61. (Can
be used as work bits when slot 1 is empty.)
CQM1H-CTB41 High-speed Counter Board:
IR 200 to IR 213 (14 words): Used by the Board
IR 214 and IR 215 (2 words): Not used.
CQM1H-SCB41 Serial Communications Board:
IR 200 to IR 207 (8 words): Used by the Board
IR 208 to IR 215 (8 words): Not used.
Used to store the analog settings when a
CQM1H-AVB41 Analog Setting Board is
mounted. (Can be used as work bits when an
Analog Setting Board is not mounted.)
Used to store the present values of high-speed
counter 0. (Can be used as work bits when
high-speed counter 0 is not being used.)
These bits are allocated to the Inner Board
mounted in slot 2. (Can be used as work bits
when a CQM1H-CPU11/21 is being used or slot
2 is empty.)
CQM1H-CTB41 High-speed Counter Board:
IR 232 to IR 243 (12 words): Used by the Board
CQM1H-ABB21 Absolute Encoder Interface
Board:
IR 232 to IR 239 (8 words): Used by the Board
IR 240 to IR 243 (4 words): Not used.
CQM1H-PLB21 Pulse I/O Board:
IR 232 to IR 239 (8 words): Used by the Board
IR 240 to IR 243 (4 words): Not used.
CQM1H-MAB42 Analog I/O Board:
IR 232 to IR 239 (8 words): Used by the Board
IR 240 to IR 243 (4 words): Not used.
These bits serve specific functions such as flags
and control bits.
These bits store data and retain their ON/OFF
status when power is turned off.
Function
Section 2-1

Related parts for CS1W-CN713