CS1W-CN713 Omron, CS1W-CN713 Datasheet - Page 92

no-image

CS1W-CN713

Manufacturer Part Number
CS1W-CN713
Description
"CABLE CS1 EXP I/O,70cm"
Manufacturer
Omron
Datasheet

Specifications of CS1W-CN713

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
70
Output Unit Specifications
Terminal Connections
Item
Note If the output current of any output exceeds the detection current, the outputs
will be turned OFF at the four points (OUT0 to 3 or OUT4 to 7) which include
that output. At the same time, the alarm output (ALM0 or ALM 1) will turn ON
and the alarm indicator will light.
If an alarm output turns ON, first eliminate the problem that caused the detec-
tion current to be exceeded. Then turn from ON to OFF the reset input (RST0
or RST1) on the side where the alarm output turned ON. The alarm output
indicator will then turn off, the alarm output will return to OFF, and the con-
tact’s output will be restored.
ALM0
ALM1
OUT1
OUT3
OUT5
OUT7
RST0
RST1
OUT0
OUT2
OUT4
OUT6
COM
COM
NC
NC
0 V
0 V
A0
A1
A2
A3
A4
A5
A6
A7
A8
B0
B1
B2
B3
B4
B5
B6
B7
B8
CQM1-OD215
Note Do not reverse the polarity of the
load power supply. If the load
power su ppl y i s conne c te d
incorrectly, the loads may not
operate correctly.
Section 2-3

Related parts for CS1W-CN713