3RW3014-1BB14 SIEMENS, 3RW3014-1BB14 Datasheet - Page 23

SIRIUS SOFTSTARTER, S00, 6.5A, 3KW/400V

3RW3014-1BB14

Manufacturer Part Number
3RW3014-1BB14
Description
SIRIUS SOFTSTARTER, S00, 6.5A, 3KW/400V
Manufacturer
SIEMENS
Datasheet

Specifications of 3RW3014-1BB14

Supply Voltage Range
200Vac To 480Vac
No. Of Phases
Three
Power Rating
3kW
Current Rating
6.5A
Operating Temperature Range
-25°C To +60°C
Approval Bodies
CE, IEC, UL, CSA
Control Voltage
RoHS Compliant
1)
1)
Electrostatic discharge (ESD)
Electromagnetic RF fields
Conducted RF interference
RF voltages and RF currents on cables
• Burst
• Surge
EMC interference field strength
Radio interference voltage
Degree of noise suppression A (industrial applications)
Degree of noise suppression B (applications for residential areas)
Control voltage
• 230 V AC/DC
• 24 V AC/DC
Soft starter types
3RW30 36
3RW30 37
3RW30 38
3RW30 46
3RW30 47
Electromagnetic compatibility according to EN 60947-4-2
EMC interference immunity
EMC interference emission
Radio interference suppression filters
Degree of noise suppression B cannot be obtained through the use of
filters as the strength of the electromagnetic field is not attenuated by the
filter.
The radio interference suppression filter is used to remove the conducted
interference from the main circuit. The field-related emissions comply with
degree of noise suppression B.
Rated current
Soft starters
A
106
45
63
72
80
Voltage range 200 ... 480 V
Filter types
4EF1512-1AA10
4EF1512-2AA10
4EF1512-3AA10
4EF1512-3AA10
4EF1512-4AA10
Recommended filters
© Siemens AG 2008
1)
Standard
EN 61000-4-2
EN 61000-4-3
EN 61000-4-6
EN 61000-4-4
EN 61000-4-5
EN 55011
EN 55011
Not required
Not available
Not required for 3RW30 1. and 3RW30 2.;
required for 3RW30 3. and 3RW30 4. (see table)
Rated current filters
A
120
50
66
90
90
1)
Siemens LV 1 N SIRIUS Soft Starters · 01/2008
Parameters
±4 kV contact discharge, ±8 kV air discharge
Frequency range: 80 ... 2000 MHz with 80 % at 1 kHz
Degree of severity 3: 10 V/m
Frequency range: 150 kHz ... 80 MHz with 80 % at 1 kHz
Interference 10 V
±2 kV/5 kHz
±1 kV line to line
±2 kV line to earth
Limit value of Class A at 30 ... 1000 MHz,
limit value of Class B at 3RW30 2.; 24 V AC/DC
Limit value of Class A at 0.15 ... 30 MHz,
limit value of Class B for 3RW30 2.; 24 V AC/DC
3RW Soft Starters
for standard applications
Terminals
mm
16
25
25
25
50
2
3RW30
6/17