RELAY CARD-INT SOLA HEVI DUTY, RELAY CARD-INT Datasheet - Page 28

no-image

RELAY CARD-INT

Manufacturer Part Number
RELAY CARD-INT
Description
Intellislot Relay Card
Manufacturer
SOLA HEVI DUTY
Datasheet

Specifications of RELAY CARD-INT

Features
Provides Dry Contact Relay Outputs For Custom Wired Applications And Delivers Support For Built-in Shutdown For AS/400 Systems
Accessory Type
Relay Card
For Use With
S4K5U
Lead Free Status / RoHS Status
na
10.0 C
10.1
10.2
Communications Interface Port
The S4K5U UPS has a standard DB-9 serial port female connector located on the rear of the UPS
unit. Several signals are provided on this port and are assigned as follows:
Table 2
Pin 4 - Remote Shutdown on Battery
1. 1. This pin is functional only when the UPS is in battery mode. If the UPS is being powered by the
2. 2. Pin 4 requires a 5-12 VDC signal to shutdown. This normally comes form the serial port using
3. 3. A battery shutdown signal on Pin 4 will NOT cause an immediate Shutdown. A shutdown
4. 4. If the mains returns during the 2-minute timer countdown, the shutdown timer will continue
Whether the UPS turns back ON when power is restored depends on the auto-restart setting: enabled
or disabled.
If the auto-restart is disabled, the UPS will not restart after performing the 2-minute shutdown
delay.
* Maximum voltage and current on pins 1, 7, 8 and 9 are 60VDC and 10.0 mA
DB-9
OMMUNICATIONS
Pin
1
2
3
4
5
6
7
8
9
mains, Pin 4 will ignore any signal on this pin.
Sola/Hevi-Duty's contact closure cable. It cannot be used with just a contact closure unless the
relay is used to switch a voltage source. A 5-12 VDC signal for 1.5 seconds or greater is required to
signal a shutdown. Signals for less than 1.5 seconds will be ignored. After Pin 4 receives a
shutdown signal for 1.5 seconds, the command cannot be canceled.
signal will start a 2-minute shutdown timer. The timer cannot be stopped. After 2 minutes, the
UPS will shut down.
until the end of 2 minutes and the UPS will turn OFF. The UPS must remain OFF for at least
10 seconds even if AC input power Returns before the UPS turns OFF. This serves to reset and
restart the server.
1
Assignment Description
Low Battery (open collector)
UPS TxD (typically RS-232 levels)
UPS RxD (typically RS-232 levels)
Remote Shutdown (5-12VDC, 10-24mA max; battery operation)
Common
Remote Shutdown (short to pin 5); all modes of operation
Low Battery (open emitter)
Mains Fail (open emitter)
Mains Fail (open collector)
Pin Assignment
6
DB-9 pin assignment
2
7
3
8
4
9
5
Collector to Emitter*
22
3 3 0 O h m s
( + )
( - )
O p e n
C o l l e c t o r
O p e n
E m i t t e r
Communications