ZA277Y Wiremold, ZA277Y Datasheet - Page 3

Suppressors, Outlet

ZA277Y

Manufacturer Part Number
ZA277Y
Description
Suppressors, Outlet
Manufacturer
Wiremold
Series
ZoneMasterr
Datasheets

Specifications of ZA277Y

Suppressor Type
Outlet Strip
Voltage Rating
277VAC
Operating Voltage Range
277VAC To 480VAC
Peak Surge Current
90kA
Connector Type
Terminal Lugs, 4 Wire (#2 AWG Max.)
Data Line Protection
N
Product
Power Outlet Strips
Breakdown Voltage Vbr
700V
Supply Voltage Min
277VAC
Rohs Compliant
No
Applications
Distribution Boards And Small Service Entrance Locations
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
ZoneMaster 450
The ZoneMaster 450 Series is designed
to protect a high-exposure main service
entrance against the most extreme
transient environment. Dual protection
circuits provide redundancy ensuring the
site is always protected. Engineered to
provide decades of uninterrupted surge
protection, the ZoneMaster 450 provides
the lowest suppression voltages available
and full protection in all modes (L-N, L-G,
L-L, and N-G).
Mechanical Specifications:
ZoneMaster 450 is 20% to 50% smaller in size than other protectors claiming similar performance. Small size means easier
installation and a better installation since the protector can often be located closer to the panel thereby minimizing the effect
of connecting lead length.
Enclosure:
Dimensions:
Weight:
Operating Environment: -40°C to 85°C, 95% relative humidity (non-condensing)
Construction:
Terminal Lugs:
Mounting:
Module Replacement:
Module Dimensions:
Standard internal disconnect. With optional fused
disconnect at no additional charge.
Remote monitoring unit.
ZONEMASTER 450
Durable, lightweight, corrosion resistant high impact plastic. Ultraviolet stabilized UL94-5V rated.
NEMA 1, 2, 3, 3S, 4, 4X 12, and 13. Transparent cover for maximum visibility and safety.
16" x 14" x 7" (41cm x 36cm x 18cm).
Approx. 20 lbs. (9 kg)
Ultra low impedance assembly. Modules are bolted to a corrosion resistant, tin plated copper bus bar.
No plug-in modules in the surge path.
#2 AWG max wire size
0.31" (8mm) diameter holes 16 3/4" x 12" [43cm x 30cm]. Enclosure can be easily drilled for
conduit/cable access.
Power should be disconnected prior to module replacement. Remove two 1/4" nuts, unplug
remote indication connector and remove module. Estimated replacement time 2 minutes.
1 1/4" x 5 5/16" x 2 1/2" [3.2cm x 13.5cm x 6.4cm]
MAXIMUM SURGE CURRENT FOR EACH PROTECTION MODE
300,000A
L-N
See page 15 for complete specifications on options.
ZoneMaster 450 Options
150,000A
Electrical Specifications
L-G
450,000A
3
L-L
EMI/RFI noise filter. Noise attenuation -75dB
maximum 100 kHz to 100 MHz.
Multi-mode surge counter.
75,000A
N-G
MAXIMUM SURGE CURRENT
PER PHASE
450,000A