ZA277Y Wiremold, ZA277Y Datasheet - Page 5

Suppressors, Outlet

ZA277Y

Manufacturer Part Number
ZA277Y
Description
Suppressors, Outlet
Manufacturer
Wiremold
Series
ZoneMasterr
Datasheets

Specifications of ZA277Y

Suppressor Type
Outlet Strip
Voltage Rating
277VAC
Operating Voltage Range
277VAC To 480VAC
Peak Surge Current
90kA
Connector Type
Terminal Lugs, 4 Wire (#2 AWG Max.)
Data Line Protection
N
Product
Power Outlet Strips
Breakdown Voltage Vbr
700V
Supply Voltage Min
277VAC
Rohs Compliant
No
Applications
Distribution Boards And Small Service Entrance Locations
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
ZoneMaster 300
The ZoneMaster 300 Series is engineered
to withstand the most severe transient
environment at large service entrance or
distribution panels, and provide decades
of uninterrupted surge protection. Dual
protection circuits provide redundancy
ensuring the site is always protected. The
ZoneMaster 300 provides the lowest
suppression voltages available, 150kA
surge capacity per mode, as well as full
protection in all modes (L-N, L-G, L-L,
and N-G).
Mechanical Specifications:
* Testing per ANSI/IEEE C62.45
Mechanical Specifications (with Disconnect):
Dimensions:
Weight:
Construction:
Mounting:
Enclosure:
Dimensions:
Weight:
Operating Environment: -40°C to 85°C, 95% relative humidity (non-condensing)
Construction:
Terminal Lugs:
Mounting:
Module Replacement:
Module Dimensions:
Remote monitoring unit.
EMI/RFI noise filter. Noise attenuation -75dB
maximum 100 kHz to 100 MHz.
ZONEMASTER 300
120/240V Single Ø 3 Wire 150kA
120/208V 3Ø 4 Wire WYE 150kA
277/480V 3Ø 4 Wire WYE 150kA
SERVICE VOLTAGE
300 SERIES
Durable, lightweight, corrosion resistant high impact plastic. Ultraviolet stabilized UL94-5V rated.
NEMA 1, 2, 3, 3S, 4, 4X 12, and 13. Transparent cover for maximum visibility and safety.
12" x 12" x 6" (31cm x 31cm x 15.5cm).
Approx. 12 lbs. (5.5 kg)
Low impedance assembly. Modules are bolted (1/4" bolts) to a large surge return plate to minimize
transient impedance and suppression voltage.
#2 AWG max wire size
4" x 0.31" diameter holes 12 3/4" x 10" [30.5cm x 25.4cm]. Enclosure can be easily drilled for
conduit/cable access.
Power should be disconnected prior to module replacement. Remove two 1/4" nuts, unplug
remote indication connector and remove module. Estimated replacement time 2 minutes.
1 1/4" x 5 5/16" x 2 1/2" [3.2cm x 13.5cm x 6.4cm]
16" x 14" x 7" (41cm x 36cm x 18cm).
Approx. 20 lbs. (9 kg)
Ultra low impedance assembly. Modules are bolted to a corrosion resistant, tin plated copper bus bar.
No plug-in modules in the surge path.
0.31" (8mm) diameter holes 16 3/4" x 12" [43cm x 30cm]. Enclosure can be easily drilled for
conduit/cable access.
MAXIMUM SURGE CURRENT FOR EACH PROTECTION MODE
150,000A
Electrical Specifications With Fused Disconnect
L-N
See page 15 for complete specifications on options.
SUPPRESSION VOLTAGE
400V
400V
800V
L-N
ZoneMaster 300 Options
150,000A
LEVELS (UL1449)
Electrical Specifications
L-G
300,000A
400V
400V
800V
L-G
5
L-L
Multi-mode surge counter. Requires selection of internal
or fused disconnect option.
Internal or fused disconnect.
CAT B3:3KA
ANSI/IEEE C62.41-1992*
75,000A
350V
350V
760V
(1.2/50µs – 8/20µs)
N-G
CAT C3:10KA
446V
446V
886V
MAXIMUM SURGE CURRENT
PER PHASE
300,000A
MAXIMUM SURGE
PER PHASE
CURRENT
300,000A
300,000A
300,000A