ZA277Y Wiremold, ZA277Y Datasheet - Page 4

Suppressors, Outlet

ZA277Y

Manufacturer Part Number
ZA277Y
Description
Suppressors, Outlet
Manufacturer
Wiremold
Series
ZoneMasterr
Datasheets

Specifications of ZA277Y

Suppressor Type
Outlet Strip
Voltage Rating
277VAC
Operating Voltage Range
277VAC To 480VAC
Peak Surge Current
90kA
Connector Type
Terminal Lugs, 4 Wire (#2 AWG Max.)
Data Line Protection
N
Product
Power Outlet Strips
Breakdown Voltage Vbr
700V
Supply Voltage Min
277VAC
Rohs Compliant
No
Applications
Distribution Boards And Small Service Entrance Locations
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Electrical Specifications:
NOTE: Maximum surge current ratings and repetitive ratings are the result of independent testing.
The extensive independent testing performed on ZoneMaster 450 with multiple test waveforms confirms ZoneMaster 450 will
tolerate and protect against the most severe electrical environments. This evidence is supported by extensive field experience
in areas known for lightning activity such as Africa and the Far East.
Surge Protection Performance:
The key performance parameter of any surge protector is how well it controls surges. At the service entrance and main panel, the
lower the voltage let-through to the facility the better the protection. A high let-through voltage at the facility entrance will stress
other equipment and small surge protectors located within the facility.
The ZoneMaster 450 surge performance figures include the fused disconnect. The surge protection performance of competitive
products significantly deteriorate when the “disconnect” option is chosen.
Maximum Continuous Operating Voltage:
Remote Indication Contacts:
Module Diagnostics:
Protection Technology:
Module Protection:
Standard Internal Disconnect:
Redundant Protection Stages in all Modes:
ZONEMASTER 450
ZONEMASTER 450 w/FILTER
ZONEMASTER 450 w/o FILTER
ZONEMASTER 450 w/FILTER
ZONEMASTER 450 w/o FILTER
PRODUCT SERIES
PRODUCT SERIES
330V
400V
MAXIMUM SURGE
L-N
700V
800V
L-N
PER MODE
CURRENT
SUPPRESSED VOLTAGE RATINGS
300,000A
SUPPRESSED VOLTAGE RATINGS
Duty Cycle Performance (Surge Life)
120V Models With Fused Disconnect
277V Models With Fused Disconnect
INDEPENDENT UL1449
INDEPENDENT UL1449
330V
400V
700V
800V
L-G
L-G
25% above nominal
NO/NC, 125VAC, 2A rated
Protection present – Green LED. Fault warning – Mechanical flag (fuse link
operated). High voltage neutral to ground – Red LED.
Patented large block, three terminal MOVs.
Dual thermal and short circuit fusing mechanisms; UL94-5V rated
plastic enclosure.
600VAC, 200,000A RMS Symmetrical Rating. Optional fused disconnect
features 200,000 AIC fusing.
Each module contains dual independent redundant protection circuits.
REPETITIVE SURGE
1500V
1500V
700V
800V
(≥4 IMPULSES
L-L
L-L
PER MODE)
CURRENT
200,000A
4
400V
400V
400V
400V
N-G
N-G
MAXIMUM NUMBER
653V
300V
OF CURRENT
IMPULSE AT
10,000 (8/20)
B1
B1
3,500
LET-THROUGH VOLTAGE
LET-THROUGH VOLTAGE
333V
693V
ANSI/IEEE C 62.41
ANSI/IEEE C 62.45
ANSI/IEEE C 62.41
ANSI/IEEE C 62.45
B2
B2
SURGE CURRENT
LONG DURATION
(10/1,000 µS)
733V
360V
B3
B3
5,800A
517V
916V
C3
C3

Related parts for ZA277Y