CIRCUIT BREAKER, HYD-MAG, 2P, 240V, 60A

209-2-1-62-4-9-60

Manufacturer Part Number
209-2-1-62-4-9-60
Description
CIRCUIT BREAKER, HYD-MAG, 2P, 240V, 60A
Manufacturer
AIRPAX
Series
209r
Datasheet

Specifications of 209-2-1-62-4-9-60

Input Voltage Vac
240V
No. Of Poles
2
Current Rating
60A
Interrupting Capacity
5kA
Trip Time
18s
Voltage Rating Vdc
0V
Trip Time Max
18sec
Trip Time Min
2sec
Mounting Type
Panel
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
177
Notes: DCR and impedance based on 100% rated current applied and
stablized a minimum of one hour.
Tolerance: .1 amperes to 1.0 amperes, ± 10%; 1.1 amperes to 5.0 amperes, ±
15%; 5.1 amperes to 15 amperes, ± 50%.
Where applicable, mechanical support must be provide to the terminals when
applying torque
0.05
0.10
0.50
1.0
5.0
10.0
15.0
20.0
30.0
209/219/229 SPECIFICATIONS
NOMINAL DCR / IMPEDANCE
APPROxIMATE CIRCUIT BREAKER WEIgHT
RECOMMENDED TORQUE SPECIFICATIONS
Current Ratings
# of Poles
1/4-20 Screw Terminals
1/4 - 20 Stud Terminals
6-32 Mounting Inserts
M3 Mounting Screws
(Amps)
1
2
3
4
5
6
10-32 Stud Terminals
M5 Stud Terminals
209/219/229/249/279 Series - Specifications
Component
51, 52, 53
460
155
4.5
1.2
.059
.0140
.0092
.0052
.0036
Resistance (ohms)
DC Delays
3 lb, 12 oz
1 lb, 3 oz
2 lb, 7 oz
Ounces
9 oz
2 lb
3 lb
Torque (in-lbs)
61, 62, 63
582
119.0
4.1
1.08
.048
.0134
.0070
.0050
.0035
35 to 40
13 to 14
13 to 14
40 to 45
6 to 8
4 to 5
Impedance (Ohms)
AC, 50/60Hz Delays
Trip Free
Will trip open on overload, even when forcibly held on. This
prevents the operator from damaging the circuit by holding
the handle in the ON position.
Trip Indication
The operating handle moves positively to the OFF position
on overload.
Environmental Specifications
Moisture and fungus resistance is provided by the use of
moisture resistant finishes. Special springs and treatment
for all ferrous parts eliminate inherent moisture-related
problems. The use of fungi inert cases and handles avoids
fungus-related problems.
Current Ratings
209/219/229 may be supplied with these ratings: DC,
50/60Hz, 400Hz, 0.1 to 100 amperes. 279 types may be
supplied with DC ratings only, 0.1 to 100 amperes.
Voltage Ratings
On 209/219/229, voltages up to and including 240Vac,
50/60Hz or 400Hz, or 125Vdc are available. Multi-pole units
can be supplied for 277Vac/480Vac, 50/60Hz. 279 types are
available with a voltage of 160Vdc. All units will be marked
with the standard maximum voltage. UL Listed breakers will
be labeled with the UL listed voltage.
Auxiliary Switch Ratings
When supplied shall be S.P.D.T. configuration with a
maximum rating of 10 amperes 250Vac.
Mounting Considerations
A three-inch spacing must be provided between the circuit
breaker and vent and any conductive surface. If closer than
three inches is necessary, then an insulator must be
installed on the conductive surface.
Solderless Connectors
Connectors are rated AL9 CU. and accept either copper or
aluminum conductors. Units are suitable for use with both
60° and 75° wire. Optional pressure plate for fine stranded
wire is available. Contact factory for details.
http://airpax.sensata.com/