60198 SQUARE D, 60198 Datasheet - Page 12

MINIATURE CIRCUIT BREAKER 240V 30A

60198

Manufacturer Part Number
60198
Description
MINIATURE CIRCUIT BREAKER 240V 30A
Manufacturer
SQUARE D
Series
Multi 9r
Datasheet

Specifications of 60198

Rohs Compliant
YES
Actuator Style
Toggle
No. Of Poles
3
Current Rating
30A
Voltage Rating Vac
240V
Mounting Type
DIN Rail
12
Multi 9™ System Catalog
Section 1—Introduction
CCC Mark
07/2010
UL 489A Standard—DC Telecommunication Applications
The UL 489A Standard covers dc rated circuit breakers intended to provide branch circuit protection in
telecommunications equipment. The products are marked as UL Listed circuit breakers for use in
telecommunication equipment.
UL 486 Standard—Connection Terminals
The UL 486 Standard applies to compression wiring connection terminals. It is a requirement for
connections of a UL 489/CSA C22.2 No.5 circuit breaker. Although it is not a requirement for UL 1077
Recognized devices, UL 486 Rated terminals are included on those Multi 9 products. This allows the
user to apply field wiring directly to any of these devices, without using intermediate, UL rated terminal
blocks.
The connectors on Multi 9 devices are Rated UL 486A-B, which applies to copper conductors.
These standards apply to field-wired terminals that are an integral part of the equipment. Criteria
includes static heating tests, secureness tests, and pull-out tests.
IEC 60947-2 Standard
In countries which follow the IEC Standards, IEC 60947-2 is used for most industrial applications of
circuit protection. IEC 60947-2 does not distinguish between the two levels of protection equivalent to
UL 489/CSA C22.2 No.5 circuit breakers and 1077 supplementary protectors. Therefore, in equipment
like that illustrated in figure 3, if IEC guidelines apply, then all of the devices could be selected from the
IEC Rated portion of this catalog.
IEC 60898 Standard
The IEC 60898 Standard is less stringent than 60947-2. It applies primarily to residential applications
of circuit breakers in countries adhering to IEC Standards, and is not generally applicable to OEMs.
CSA C22.2 Standard
The CSA
CSA C22.2 No. 5-02 (harmonized to UL 489/CSA C22.2 No.5) and CSA C22.2 No. 235 (equivalent to
UL 1077). All UL rated devices also have the corresponding CSA rating, unless otherwise noted.
CCC Mark
The China Compulsory Certification (CCC) mark is a new safety and quality mark system. Compulsory
Product Certification System (CPCS) prohibits the sale or importation of equipment under the scope of
the law that does not bear the CCC Mark issued by a Designated Certification Body (DCB). The CCC
Mark covers both safety and Electromagnetic compatibility.
The CPCS regulates 22 different product groups, which include the following:
Electrical wires and cables; switches for circuits, installation protective and connection devices; low-
voltage electrical apparatus; small power motors; electric tools; welding machines; household and
similar electrical appliances; audio and video apparatus; information technology equipment; lighting
apparatus; telecommunications terminal equipment; motor vehicles and safety parts; motor vehicle
tires; safety glass; agricultural machinery; latex products; medical devices; fire fighting equipment;
detectors for intruder alarm systems; wireless local area network equipment; security and protection
equipment; and decoration and renovation products.
Circuit breaker
UL Listed
UL 489/CSA C22.2 No.5
The UL symbol
®
(Canadian Standards Association
®
) C22.2 Standards closely correspond to the UL Standards:
© 2002–2010 Schneider Electric