60198 SQUARE D, 60198 Datasheet - Page 37

MINIATURE CIRCUIT BREAKER 240V 30A

60198

Manufacturer Part Number
60198
Description
MINIATURE CIRCUIT BREAKER 240V 30A
Manufacturer
SQUARE D
Series
Multi 9r
Datasheet

Specifications of 60198

Rohs Compliant
YES
Actuator Style
Toggle
No. Of Poles
3
Current Rating
30A
Voltage Rating Vac
240V
Mounting Type
DIN Rail
© 2002–2010 Schneider Electric
All Rights Reserved
Vigi Module
IEC Rated C60 Vigi
The C60 Vigi residual current detector can be added to the C60 circuit breaker to provide a high level
of protection against earth leakage faults. The Vigi module clips onto the right-hand side of a C60
protective device and is mechanically linked to the C60 circuit breaker, which it trips when the Vigi
detects residual current. Vigi modules are available for use with 2-, 3-, and 4-pole C60 circuit breakers.
The Vigi module may be field installed.
The Vigi module combines a current sensing toroid and residual current relay in one case and
operates without an auxiliary power supply source. It may be ordered with a variety of non-adjustable
sensitivities (10 to 1,000 mA). A version with time delay (selective) provides non-adjustable time delay
for coordination with downstream instantaneous residual current devices.
A built-in filtering device minimizes nuisance tripping due to transient voltages (lightning, line
disturbances, etc.) and transient currents (from high capacitive circuits).
A visual indicator of the ground fault is provided by a red flag on the Vigi operating handle. A manual
test button on the face of the Vigi module allows manual testing of the Vigi module.
The C60 Vigi module can be field-adapted to reset in one of two modes: Automatic reset when the
associated protective device handle is reset, or by manually resetting the Vigi prior to reclosing the
supplementary protector.
A version with time delay (selective) provides additional time discrimination with downstream
instantaneous residual current devices.
NOTE: The C60 version of the Vigi Module cannot be used with the C120 series. A different series of
Vigi Modules is available for the C120 devices.
Figure 10:
NOTE: Also see the ID Residual Current Switches.
Table 35:
Voltage (Nominal):
High Voltage Withstand: 6 kV
Connection: Box Lug:
Mounting
Time-Current Curves
Time/Current Curve
Sensitivities
Temperatures
See Table 29 on page 32 for weights, dimensions and interrupting ratings
C60 Circuit Breaker
Example of Residual Current Circuit Breaker
Specifications for IEC Rated C60 Vigi Modules for Ground-Fault Protection
TM
+
Modules for Ground-fault Protection
130–240 Vac
220–415 Vac
6 kV
≤ 25 Stranded 6 AWG (16 mm
≤ 25 Solid 6 AWG (16 mm
≤ 63 Stranded 6 AWG (16 mm
≤ 63 Solid 6 AWG (16 mm
Depends on Circuit Breaker
Instantaneous or Selective Release
Fixed at 10, 30, 300, or 1000 mA
Calibration
Operating
35 mm DIN rail
Vigi Module
Section 4—Ground-Fault Protection Devices
2
2
) Cu Wire
) Cu Wire
2
2
=
) Cu Wire
) Cu Wire
s
Residual Current Circuit Breaker
Multi 9™ System Catalog
+10/ -20%, 50/60 Hz
+10/ -20%, 50/60 Hz
4 N•m
2 N•m
4 N•m
3.5 N•m
77°F (25°C)
22 to 140°F (-5 to 60°C)
07/2010
37

Related parts for 60198