CIRCUIT BREAKER, THERMAL MAG, 3P, 100A

EGB3100FFG

Manufacturer Part Number
EGB3100FFG
Description
CIRCUIT BREAKER, THERMAL MAG, 3P, 100A
Manufacturer
EATON CUTLER HAMMER
Series
Gr
Datasheet

Specifications of EGB3100FFG

Actuator Style
Toggle
No. Of Poles
3
Current Rating
100A
Voltage Rating Vdc
250V
Voltage Rating Vac
480V
Mounting Type
DIN Rail
Terminals
Screw
November 2008
Low Energy Shunt Trip
fault protection schemes. However,
with a proper control voltage source,
they may be applied in place of
conventional trip devices for special
applications. Flux paths surrounding
permanent magnets used in the shunt
trip assembly hold a charged spring
poised in readiness to operate the
circuit breaker trip mechanism.
Table 12-428. F-, J-, K-, L-, M-, N- and R-Frames and HMCPs Low Energy Shunt Trip
F-Frame
J-Frame
K-Frame
L- and M-Frames
N-Frame
R-Frame
CA08101001E
Mounting
Positions
(Pole)
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Cutoff provisions required in control circuit.
Listed with Underwriters Laboratories for field installation under E64983.
Standard mounting location — leads exit rear of breaker.
For F-Frame HMCP, add an “M” to beginning of catalog number.
For use with thermal-magnetic trip units only.
Breakers with K-Frame OPTIM 550 can only accept accessories in left pole.
UV
L
devices are designed to
operate from low energy
output signals from dedi-
cated current sensors typi-
cally applied in ground
o
w Energy Shunt Trip
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Same Side
Suffix
Number
NO1
NO5
NO1
NO5
NO1
NO5
NO1
NO5
NO1
NO1
Adder
U.S. $
Suffix
Number
NO2
NO6
NO2
NO6
NO2
NO6
NO2
NO6
Rear
NO2
When a 100 microfarad capacitor
charged to 28 Vdc is discharged
through the shunt trip coil, the result-
ant flux opposes the permanent mag-
net flux field, which releases the
stored energy in the spring to trip the
circuit breaker. As the circuit breaker
resets, the shunt trip reset arm is actu-
ated by the circuit breaker handle,
resetting the shunt trip. The plug-in
module is mounted in retaining slots
in the top of the trip unit. Coil is inter-
mittent-rated only. Cutoff provisions
required in control circuit.
For more information visit: www.eaton.com
Series C Molded Case Circuit Breakers
Internal Accessories
Low Energy Shunt Trip
Adder
U.S. $
Opposite Side
Suffix
Number
NO3
NO7
NO3
NO7
NO3
NO7
NO3
NO7
NO3
Adder
U.S. $
Terminal Block
Same Side
Suffix
Number
NO4
NO8
Adder
U.S. $
Ordering Information
Select shunt trip catalog number
for the voltage within the indicated
voltage range. Shunt trip coils are
designed to be applied at specific
ac or dc voltages within the voltage
range shown. Electrical ratings are
also shown on applicable circuit
breaker accessory nameplates.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CB-2
Field Mounted
Catalog
Number
LST1LPK
LST1RPK
LST2LPK
LST2RPK
LST3LPK
LST3RPK
LST4LPK
LST4RPK
LST5LPK
LST6RPK
Field Installation Kits
Pigtail Leads
Price
U.S. $
Catalog
Number
LST1LTK
LST1RTK
Terminal Block
Price
U.S. $
12-231