EGB3100FFG EATON CUTLER HAMMER, EGB3100FFG Datasheet - Page 60

CIRCUIT BREAKER, THERMAL MAG, 3P, 100A

EGB3100FFG

Manufacturer Part Number
EGB3100FFG
Description
CIRCUIT BREAKER, THERMAL MAG, 3P, 100A
Manufacturer
EATON CUTLER HAMMER
Series
Gr
Datasheet

Specifications of EGB3100FFG

Actuator Style
Toggle
No. Of Poles
3
Current Rating
100A
Voltage Rating Vdc
250V
Voltage Rating Vac
480V
Mounting Type
DIN Rail
Terminals
Screw
12
12-60
Motor Circuit 480 Vac, Protectors — Selection Guide and Ordering Information
Table 12-104. EG-Frame — 480 Vac, 600Y/347 Vac Maximum
Continuous
Amperes
100
100
15
30
50
70
UL listed for use with Cutler-Hammer Motor Starters.
Motor FLA ranges are typical. The corresponding trip setting is at
13 times the minimum FLA value shown. Where a 13 times setting is
required for an intermediate FLA value, alternate cam settings and/or
MCP ratings should be used.
For dc applications, actual trip levels are approximately 40% higher
than values shown.
Settings above 10 x I n are for special applications. Where the ampere
rating of the disconnecting means cannot be less than 115% of the
motor full load ampere rating.
3
7
Series G Molded Case Circuit Breakers
15 – 2500 Amperes for UL, CSA & IEC Applications
Motor Circuit Protectors
Cam
Setting
A
B
C
D
E
F
A
B
C
D
E
F
A
B
C
D
E
F
A
B
C
D
E
F
A
B
C
D
E
F
A
B
C
D
E
F
A
B
C
D
E
F
A
B
C
D
E
F
Motor
Full Load
Current
Amperes
1.1 – 1.3
1.6 – 1.7
2.0 – 2.2
2.3 – 2.5
2.6 – 2.8
10.4 – 11.4
11.5 – 12.6
12.7 – 13.0
11.5 – 13.7
16.1 – 18.3
20.7 – 22.9
23.0 – 25.2
25.3 – 26.1
11.5 – 15.2
19.2 – 22.9
26.9 – 30.6
34.6 – 38.3
38.4 – 42.1
42.2 – 43.5
16.1 – 30.6
26.9 – 32.2
37.6 – 42.9
48.4 – 53.7
53.8 – 59.1
59.2 – 60.9
23.0 – 30.6
38.4 – 46.0
53.8 – 61.4
69.2 – 76.8
76.9 – 84.5
84.6 – 87.0
38.4 – 46.0
57.6 – 65.2
76.9 – 84.5
.69 – .91
1.5 – 2.0
2.6 – 3.1
3.7 – 3.9
4.8 – 5.2
5.3 – 5.7
5.8 – 6.1
3.4 – 4.5
5.7 – 6.8
8.0 – 9.1
3.9 – 9.1
MCP
Trip
Setting
1000
1100
1000
1250
1375
1500
105
135
150
165
150
210
270
300
330
150
250
350
450
500
550
210
350
490
630
700
770
300
500
700
900
500
750
15
21
27
30
33
21
35
49
63
70
77
45
75
90
9
MCP
Catalog
Number
HMCPE003A0C
HMCPE007C0C
HMCPE015E0C
HMCPE030H1C
HMCPE050K2C
HMCPE070M2C
HMCPE100R3C
HMCPE100T3C
For more information visit: www.eaton.com
Price
U.S. $
Table 12-105. JG-Frame — 600 Vac Maximum, 250 Vdc Maximum
Table 12-106. LG-Frame — 600 Vac Maximum, 250 Vdc Maximum
Note: 800 and 1200 ampere, 600 Vac maximum motor circuit
protectors are available as Series C HMCP product.
Continuous
Amperes
250
Continuous
Amperes
600
UL listed for use with Cutler-Hammer Motor Starters.
Equipped with an electromechanical trip device.
UL listed for use with Cutler-Hammer Motor Starters.
MCP
Trip Range
(Amperes)
1000 – 2000
1125 – 2250
1250 – 2500
MCP
Trip Range
(Amperes)
1250 – 2500
1500 – 3000
1750 – 3500
2000 – 4000
2250 – 4500
2500 – 5000
3000 – 6000
500 – 1000
625 – 1250
750 – 1500
875 – 1750
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . CB-2
MCP
Catalog
Number
HMCPJ250D5L
HMCPJ250F5L
HMCPJ250G5L
HMCPJ250J5L
HMCPJ250K5L
HMCPJ250L5L
HMCPJ250W5L
MCP
Catalog
Number
HMCPL600L6G
HMCPL600N6G
HMCPL600R6G
HMCPL600X6G
HMCPL600Y6G
HMCPL600P6G
HMCPL600M6G
November 2008
CA08101001E
Price
U.S. $
Price
U.S. $

Related parts for EGB3100FFG