K2CU-F40A-C AC16-40AAC100 Omron, K2CU-F40A-C AC16-40AAC100 Datasheet - Page 7

no-image

K2CU-F40A-C AC16-40AAC100

Manufacturer Part Number
K2CU-F40A-C AC16-40AAC100
Description
HEATER FAULT DETECTOR
Manufacturer
Omron
Series
K2CUr
Datasheets

Specifications of K2CU-F40A-C AC16-40AAC100

Current Rating
16 ~ 40 A
Mounting Type
Panel
Operational Type
Large, Built in Transformer
Voltage - Supply
100 VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Gate Input
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
K2CU-F40A-CAC16-40AAC100
K2CUF40ACAC1640AAC100
In a Three-phase, V Network 1
Set the operating current to be 0.3 to 0.35 times the heater current.
Close the SW
indicator remains off.
Turn off SW
the output relay operates.
K2CU-F, K2CU-P
The operation of the heater burnout detector can be easily checked as follows:
In a Single-phase Circuit
Set the operating current to be 0.55 to 0.6 times the heater current.
Close the contactor with switch SW
alarm indicator remains off.
Turn off SW
the output relay operates.
1
1
and confirm that the alarm indicator comes on, and that
and confirm that the alarm indicator comes on, and that
2
with switch SW
http://www.ia.omron.com/
K2CU-F
S
S
1
1
2
turned on. Confirm that the alarm
SW
Heater
1
SSR
1
turned on. Confirm that the
SW
2
In a Three-phase, V Network 2
Set the operating current to be 0.6 times the heater current (of the
phase connected between terminals 1 and 2, or the one passed
through the window of the window-type Current Transformer of the
heater burnout detector).
Close the SW
indicator remains off.
Turn off SW
the output relay operates.
(c)Copyright OMRON Corporation 2008 All Rights Reserved.
SW
S
S
SW
1
1
2
1
and confirm that the alarm indicator comes on, and that
1
Heater
2
SSR
Heater
with switch SW
K2CU-F
Contactor
S
S
1
2
SW
1
2
turned on. Confirm that the alarm
SW
1
K2CU-F
Heater
Contactor
8
1
2
K2CU
K2CU-P
6
7