GT3F-1AD24 IDEC, GT3F-1AD24 Datasheet - Page 36

no-image

GT3F-1AD24

Manufacturer Part Number
GT3F-1AD24
Description
GT3F-1AD24 8PIN DPDT TRUE POWER OFF DELAY TIMER
Manufacturer
IDEC
Datasheet
840
Inputs Inputs
To avoid electric shock, do not touch the input signal terminal during power voltage application.
When connecting the input signal terminals of two or more GT3A timers to the same contact or transistor, the input terminals of the same number should be con-
nected. (Connect Terminals No.2 in common.)
[Incorrect]
Input
Contact or Transistor
In a transistor circuit for controlling input signals, with its primary and secondary power circuits isolated, do not ground the secondary circuit.
Connect the input signal terminals of the GT3A timers to Terminal No.2 only. Never apply voltage to other terminals; otherwise, the internal circuit may be damaged.
Input signal lines must be made as short as possible and installed away from power cables and power lines. Use shielded wires or a separate conduit for
input wiring.
5, 6, and 7
Input Terminal
2
Insulating Transformer
2
2
Circuit
GT3 Series
Timer
10
Input
Terminal
Input
Terminal
GT3 Series
Timer
Input
Terminal
R
10
10
Y
GT3 Series Instructions
Power
Power
Power
[correct]
Instructions: Wiring Inputs for GT3 Series
2
2
Input
Terminal
Input
Terminal
10
10
Power
www.idec.com
Timers