61F-GP-NH AC100 Omron, 61F-GP-NH AC100 Datasheet - Page 35

no-image

61F-GP-NH AC100

Manufacturer Part Number
61F-GP-NH AC100
Description
LEVEL CONTROL
Manufacturer
Omron
Series
61Fr
Type
Level Control - High Sensitivityr
Datasheets

Specifications of 61F-GP-NH AC100

Applications
Supply and Drain Control
Mounting Type
Socket Mount (11 pos)
Voltage - Supply
100 VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
61F-GP-NHAC100
61FGPNHAC100
61F-APN2
Connect the output terminal Ta of the 61F-Gj to input terminal 2 of the 61F-APN2.
Connection
Connect the contactor coil terminal A to the switching contact terminals 3 and 4 of the 61F-APN2.
Operation of the two pumps can be displayed using the switching contact terminals 5 and 6 of the 61F-APN2.
Timing Chart of Water Supply Alternate Operation
When the 61F-APN2 Alternate Operation Relay is used in combina-
tion with a 61F Controller, the output contacts of the Alternate
Operation Relay will not be switched (OFF) while the contactor is
being excited, and the contactor will not be excited (ON) at the mo-
ment when the output contacts are switched. That is, loads such as
contactors will not be directly turned ON or OFF by the actions of the
output contacts of the 61F-APN2 Alternate Operation Relay.
Instead, they will be turned ON or OFF by the actions of the 61F
Controller.
61F-APN2
Output contact between
1 and 4 and 5 and 8
Output contact between
1 and 3 and 6 and 8
Power supply voltage
between 2 and 7
Power
Output
1-3
Output
1-4
Contact 1
Contact 2
61F
40 ms min.
Ta
Tb
200 ms min.
In case of water supply operation, the output contacts of the Alter-
nate Operation Relay will be switched after the normally closed con-
tacts of the 61F turn OFF upon reaching the control level, and the
output contacts will be already switched when the normally closed
contacts of the 61F turn OFF next time.
Therefore, only the continuous line current needs to be considered
as the load capacity of the 61F-APN2 and the current can be applied
up to the rated line current of 3 A.
61F-APN2