EA1-B0-12-650-21A-BB Carling Technologies, EA1-B0-12-650-21A-BB Datasheet - Page 5

Circuit Breakers 50A ONE POLE

EA1-B0-12-650-21A-BB

Manufacturer Part Number
EA1-B0-12-650-21A-BB
Description
Circuit Breakers 50A ONE POLE
Manufacturer
Carling Technologies
Datasheet

Specifications of EA1-B0-12-650-21A-BB

Product Type
Circuit Breakers
Current Rating
50 Amps
Voltage Rating
600 VoltsAC, 125 VoltsDC
Trip Time
0.15 s to 0.8 s
Mounting Style
Panel
Termination Style
Threaded Stud
Circuit Function
Series Trip (Current)
Product
Hydraulic Magnetic Circuit Breakers
Number Of Poles
1 Pole
Actuator Type
Handle
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
106
E-Series Handle UL Listed – Ordering Scheme
A06
A12
A18
A24
A32
A48
7 CURRENT RATING (AMPERES)
020
025
030
035
040
045
050
055
060
065
070
075
080
085
090
090
210
215
220
225
230
OR VOLTAGE COIL (MIN. TRIP RATING, VOLTS)
1 SERIES
E
2 ACTUATOR
Handle
A
3 POLES
1
2
4 CIRCUIT
B
5 AUXILIARY SWITCH
0
2
3
4
6 FREQUENCY & DELAY
10
12
14
16
20
22
24
26
32
34
36
1
Series
E
5
5
12 DC, 10 DC
18 DC, 15 DC
24 DC, 20 DC
32 DC, 25 DC
48 DC, 40 DC
Handle, one per pole
Series Trip (Current)
without Auxiliary Switch
S.P.D.T. 0.110 Q.C. Terminals
S.P.D.T. 0.139 Solder Lug
S.P.D.T. 0.110 Q.C. Terminals
(Gold Contacts)
DC Instantaneous
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Short
50/60Hz Medium
50/60Hz Long
DC, 50/60Hz Short
DC, 50/60Hz Medium
DC, 50/60Hz Long
0.020
0.025
0.030
0.035
0.040
0.045
0.050
0.055
0.060
0.065
0.070
0.075
0.080
0.085
0.090
0.095
0.100
0.150
0.200
0.250
0.300
6 DC, 5 DC
One
Two
1
2
2
Actuator
A 2
235
240
245
250
255
260
265
270
275
280
285
290
295
410
512
415
517
420
522
425
527
3
Poles
4
A65
B25 125 DC, 100 DC
J06
J12
J18
J24
0.350
0.400
0.450
0.500
0.550
0.600
0.650
0.700
0.750
0.800
0.850
0.900
0.950
1.000
1.250
1.500
1.750
2.000
2.250
2.500
2.750
3
4
65 DC, 55 DC
7
12 AC, 10 AC
18 AC, 15 AC
24 AC, 20 AC
Three
Four
6 AC, 5 AC
4
Circuit
B
430
435
440
445
450
455
460
465
470
475
480
485
490
495
610
710
611
711
612
712
613
C
6
7
8
9
62
64
66
72
74
76
92
94
96
3
6
6
6
10.000
10.500
12.000
12.500
13.000
11.000
11.500
S.P.D.T. 0.110 Q.C. Terminals
S.P.D.T. 0.110 Q.C. Terminals
(Gold Contacts)
S.P.D.T. 0.187 Q.C. Terminals
S.P.D.T. 0.187 Q.C. Terminals
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC, Short,Hi-Inrush
DC, Medium, Hi-Inrush
DC, Long, Hi-Inrush
DC, 50/60Hz Short, Hi-Inrush
DC, 50/60Hz Medium,
Hi-Inrush
DC, 50/60Hz Long, Hi-Inrush
Series Trip (Voltage)
3.000
3.500
4.000
4.500
5.000
5.500
6.000
6.500
7.000
7.500
8.000
8.500
9.000
9.500
5
Auxiliary
Switch
5
0
J48
J65
K20 120 AC, 65 AC
L40 240 AC, 130 AC
5
6
614
615
616
617
618
620
622
624
625
630
635
640
650
660
670
680
690
810 100.000
912 125.000
48 AC, 40 AC
65 AC, 55 AC
Five
Six
6
Frequency
& Delay
24 450
14.000
15.000
16.000
17.000
18.000
20.000
22.000
24.000
25.000
30.000
35.000
40.000
50.000
60.000
70.000
80.000
90.000
7
Current Rating
NOTES
1
2
3
4
5
6
7
8
9
10
11
12
13
8 TERMINAL
BACK CONNECTED (FRONT MOUNTED ONLY)
1
2
FRONT CONNECTED (BACK MOUNTED ONLY)
3
C
4
5
6
F
7
8
9
J
9 ACTUATOR COLOR & LEGEND
Actuator Color :
Color:
White
Black
Red
Green
Blue
Yellow
Gray
Orange
10 MOUNTING/BARRIERS
BACK CONNECTED (FRONT MOUNTED ONLY)
A
B
FRONT CONNECTED (BACK MOUNTED ONLY)
C
D
E
F
11 MAXIMUM APPLICATION RATING
B
C
D
12 AGENCY APPROVAL
C
F
8
8
9
9
9
10
10
10
Standard multi-pole units identical poles except when specifying auxiliary switch - (see
Note 4). For mixed ratings, consult factory. VDE Certification on 1-5 poles only.
Series Trip construction available w/either front or back connected terminals.
Series Trip construction with a voltage coil is not available as a single pole unit and must
be tied to a protected pole.
On multi-pole units, only one auxiliary switch is normally supplied mounted in the extreme
right pole per Figure A. Back mounted units require special mounting provisions when aux-
iliary switch is specified. VDE Certification on auxilary switch codes 0, 2, 3 & 4 only.
Voltage Trip Coils are not rated for continuous duty. Available only with Frequency & Delay
Codes 10 & 20.
Frequency & Delay Codes 92, 94 & 96 are not VDE Certified.
Current Ratings under 0.100 amps are not VDE Certified .
An Anti-Flash Over Barrier is supplied between poles on multi-pole units with 10-32 Stud
(Terminal Code 1) or 1/4-20 Stud (Code 2) terminals per UL requirement.
Box Wire Connector will accept #14 through 0 AWG. copper wire or #12 through 0 AWG.
aluminum wire.
Box Wire Connector with Pressure Plate for stranded wire, consult factory for details.
Back Mounted breakers can also be front mounted by utilizing the proper front panel
mounting inserts normally supplied. However, terminal connections must be made prior to
mounting.
VDE Certification requires dual (I-O , ON-OFF) markings on all handles.
Not available with VDE Certification.
13
10-32 Stud (All Terminals)
1/4-20 Stud (All Terminals)
Box Wire Connector (Line & Load)
Box Wire Connector w/ Pressure Plate (Line & Load)
10-32 Screw (Line & Load)
10-32 “Bus-Type” Screw (Line), 10-32 Screw (Load)
10-32 “Bus-Type” Screw (Line), Box Wire Connector (Load)
10-32 “Bus-Type” Screw (Line), Box Wire Connector
w/ Pressure Plate (Load)
1/4-20 Screw (Line & Load)
1/4-20 “Bus-Type” Screw (Line), 1/4-20 Screw (Load)
1/4-20 “Bus-Type” Screw (Line), Box Wire Connector (Load)
1/4-20 “Bus-Type” Screw (Line), Box Wire Connector
w/ Pressure Plate (Load)
Mounting Inserts
6-32
ISO M3
Back Mounting Foot Type
Short
Short
Long
Long
125 VDC, 100A
120/240 VAC, 100A
240 VAC, 100A
UL 489 Listed & CSA Certified
UL 489 Listed, CSA Certified, & VDE Certified
7
8
Terminal
1 2 A
Marking:
ON-OFF
B
D
G
J
L
N
Q
S
9
Actuator
Color
Dual
1
2
3
4
5
6
7
8
12
Front Mounting Inserts (Optional Use)
6-32
ISO M3
6-32
ISO M3
10
Mounting/
Barriers
Marking Color:
Black
White
White
White
White
Black
Black
Black
www.carlingtech.com
11
11
Maximum
Application
Rating
C
MAX. RATING
MAX. RATING
12
Agency
Approval
C
100 A
100 A
100 A
100 A
100 A
100 A
100 A
100 A
100 A
50 A
50 A
50 A

Related parts for EA1-B0-12-650-21A-BB