H5CX-A-N AC100-240 Omron Automation, H5CX-A-N AC100-240 Datasheet - Page 18

no-image

H5CX-A-N AC100-240

Manufacturer Part Number
H5CX-A-N AC100-240
Description
Relay; E-Mech; Timing; Multi-Function; Cur-Rtg 5A; Ctrl-V 100-240AC; REPL:H5CX-AAC1002
Manufacturer
Omron Automation
Type
Timerr
Datasheet

Specifications of H5CX-A-N AC100-240

Brand/series
H5CX
Connection Type
Screw Terminals
Contact Form
5 A at 250VAC/30 VDC
Dimensions
58H x 48W x 98.5D
Display Type
7 Segment LCD
Function
Multifunction Digital Timer
Input Type
Signal, Reset and Gate
Ip Rating
IP66
Mounting Type
Flush
Number Of Inputs
3
Number Of Outputs
1
Output Type
SPDT
Primary Type
Digital Timer
Voltage, Supply
100-240 VAC
18
H5CX-A@-N/-L@-N
Timer
Explanation of Functions
Operating Procedures for Timer Function
Items marked with stars ( ) can be set using the DIP switch.
Time Range (timr)
Set the range to be timed in the range 0.001 s to 9,999 h.
Settings of type ---- h (9,999 h) and ---- min (9,999 min) cannot be
made with the DIP switch. Use the operation keys if these settings are
required.
Timer Mode (timm)
Set either the elapsed time (UP) or remaining time (DOWN) mode.
In UP mode, the elapsed time is displayed, and in DOWN mode, the
remaining time is displayed.
Output Mode (outm)
Set the output mode.
The possible settings are A, A-1, A-2, A-3, b, b-1, d, E, F, Z and S.
Only output modes A, A-2, E, and F can be set using the DIP switch.
Use the operation keys if a different setting is required.
(For details on output mode operation, refer to "Timing Charts" on
page 20.)
Output Time (otim)
When using one-shot output, set the output time for one-shot output
(0.01 to 99.99 s).
One-shot output can be used only if the selected output mode is A,
A-1, A-2, A-3, b, b-1 or S.
If the output time is set to 0.00,
held.
Input Signal Width (iflt)
Set the minimum signal input width (20 ms or 1 ms) for signal, reset,
and gate inputs.
The same setting is used for all external inputs (signal, reset, and gate
inputs).
If contacts are used for the input signal, set the input signal width to
20 ms.
Processing to eliminate chattering is performed for this setting.
NPN/PNP Input Mode (imod)
Select either NPN input (no-voltage input) or PNP input (voltage
input) as the input format.
Set an NPN input when using a 2-wire sensor.
For details on input connections, refer to "Input Connections" on
page 9.
hold
is displayed, and the output is
Display Color (colr)
(Terminal block model: H5CX-A@ only)
Set the color used for the present value.
Key Protect Level (kypt)
Set the key protect level.
Refer to “Key Protect Level” on page 32.
Instantaneous/Time-limit (otmd)
Set the contact output to time-limit SPDT + instantaneous SPDT or
time-limit SPDT operation.
Set Value Upper Limit (sl-h)
Set the upper limit for the set value when it is set in Run Mode.
The limit can be set to between 1 and 9999.
This setting does not apply to the ON duty in Z mode.
Output ON Count Alarm Set Value (on-a)
Set the alarm value for the output ON count.
The limit can be set to between 0 x 1000 (0 times) and 9999 x 1000
(9,999,000 times). Only the underlined values are set. The alarm will
be disabled if 0 is set.
If the total ON count of the output exceeds the alarm set value,
be displayed on the Timer to indicate that the output ON count alarm
value was exceeded. Refer to “Self-diagnostic Function” on page
32 for information on the
ON Count Alarm Set Values for Outputs 1 and 2 (OUT1
and OUT2) (on1a and on2a)
Set the ON count alarm values for the outputs 1 and 2.
The limit can be set to between 0 x 1000 (0 times) and 9999 x 1000
(9,999,000 times). Only the underlined values are set. The alarm will
be disabled if 0 is set.
If the total ON count of instantaneous output 1 or 2 exceeds the alarm
set value,
ON count alarm value was exceeded. Refer to “Self-diagnostic
Function” on page 32 for information on the
Output ON Count Monitor Value (on-c)
The monitor value is only displayed. It cannot be set.
The output ON count will be 1,000 times the displayed value.
ON Count Monitor Values for Outputs 1 and 2 (OUT1 and
OUT2) (on1c and on2c)
The monitor value for output 1 or 2 is only displayed. It cannot be set.
The output ON count will be 1,000 times the displayed value.
red
grn
org
r-g
g-r
r-o
o-r
g-o
o-g
e3
will be displayed on the Timer to indicate that the output
e3
Output OFF
display.
Orange
Orange
Green
Green
Red
Red
Orange (fixed)
Green (fixed)
Red (fixed)
e3
display.
Output ON
Orange
Orange
Green
Green
Red
Red
e3
will

Related parts for H5CX-A-N AC100-240