ARA120AGE ATC Diversified Electronics, ARA120AGE Datasheet

no-image

ARA120AGE

Manufacturer Part Number
ARA120AGE
Description
Relay; E-Mech; Alternating; Cur-Rtg 10A; Ctrl-V 120AC/DC; Vol-Rtg 240AC; Pnl-Mnt
Manufacturer
ATC Diversified Electronics
Datasheet

Specifications of ARA120AGE

Brand/series
ARA Series
Current, Rating
10 A
Function
Alternating
Mounting Type
Panel
Power, Rating
360 VA
Relay Type
Electro Mechanical
Standards
cULus, CSA
Termination
#8-32 Screws
Voltage, Control
120 VAC/VDC
Voltage, Rating
240 VAC
Contact Rating
5 A @ 240 VAC. Resistive
Operating Temperature
–20°C to +55°C
Dimensions (l X W X H)
4.0" × 4.0" × 3.0"
The Triplexor and Quadraplexor Alternating Relays are designed for use in mul-
tiple load installations that are required to alternate in sequence while assur-
ing equal run time on all loads. They also allow for additional loads to run in
the event of excess load requirements.
The Triplexor and Quadraplexor have the option of automatic alterations or
external clocking alterations. When the factory installed jumper is in place
the alternating action is initiated by a control switch, which is common with
one side of the control voltage. When the jumper is removed the alternating
action is initiated by an isolated normally open switch.
ARA-XXX-AFE ALTERNATING ACTION
TRIPLEXOR: For automatic alterations a factory-installed jumper is in place
between terminals 3 and 4. The alternating action is accomplished when the
control switch between terminals 2 and 4 opens.
For external clocking alterations, remove the factory-installed jumper between
terminals 3 and 4 and place an isolated normally open switch between terminals
2 and 3. The alternating action will occur each time this isolated switch is closed
and then re-opened.
ARA-XXX-AGE
QUADRAPLEXOR: For automatic alterations, a factory installed jumper is in place between termi-
nals 11 and 12. The alternating action is accomplished when the control switch between terminals 2
and 3 opens.
For external clocking alterations, remove the factory-installed jumper
between terminals 11 and 12 and place an isolated normally open
switch between terminals 2 and 12. The alternating action will
occur each time this isolated switch is closed and then re-opened.
In the event of a power failure the Alternating Relays will return to
their quiescent state and continue sequencing loads on one-at-a-time.
\\\
\\\
800.727.5646
DIMENSIONS
WIRING
(INCHES)
atcdiversified.com
Diversified Electronics
\\\
CONTROL
VOLTAGE
CONTROL
SWITCH CURRENT
POWER REQUIRED 3 VA (Approximately)
DUTY CYCLE
OUTPUT RATING
LIFE
EXPECTANCY
INDICATORS
TEMPERATURE
RATING
ENCLOSURE
TERMINATIONS
WEIGHT
NOTE: For Analog signal inputs, ATC offers a duplexing pump
control — the ATC-Digitec 3800 Panel Meter
MODEL NUMBER
SPECIFICATIONS
24, 120 VAC ±10%, 50/60 Hz
2 mA
Continuous
LED’s Show Condition of Outputs
Style “E” Lexan
(12) #8-32 Screw Terminals
12 to 14 oz.
Quadraplexor
Mechanical
120 V Quadraplexor
Triplexor
Electrical
Operate
Storage
> > > > > >
Control Voltage
120 V Triplexor
24 V Triplexor
Quadraplexor (120 V only) G
(3) 5 Amp Resistive, 1/6 hp,
211 VA @ 120 VAC, Inductive
Externally Switched to terminal #2
(4) 5 Amp Resistive, 1/6 hp,
211 VA @ 120 VAC, Inductive
Externally Switched to terminal #2
10,000,000 Operations
(Minimum)
100,000 Operations
@ Rated Load
-4° to 131°F (-20° to +55°C)
-40° to 185°F (-40° to +85°C)
®
Surface Mounted
ARA
ARA Series
120
120
24
Triplexor
A
F
E
251

Related parts for ARA120AGE

Related keywords