CMB120AFA1 ATC Diversified Electronics, CMB120AFA1 Datasheet

no-image

CMB120AFA1

Manufacturer Part Number
CMB120AFA1
Description
Relay; E-Mech; Current Monitor; SPDT; Cur-Rtg 10A; Ctrl-V 120AC; Vol-Rtg 240AC; 8 Pin
Manufacturer
ATC Diversified Electronics
Datasheet

Specifications of CMB120AFA1

Brand/series
CMB Series
Contact Form
SPDT
Current, Rating
10 A
Function
Current Monitor
Mounting Type
Socket
Number Of Pins
8
Power, Rating
211 VA
Relay Type
Electro Mechanical
Standards
cULus
Termination
Plug-In
Voltage, Control
120 VAC
Voltage, Rating
240 VAC
FEATURES
• No physical connection to the AC line that is being
• Magnetically coupled by passing supply line through
• Heavy Duty Contacts
• 8-Pin, Plug-in
• Low Cost
• Easy Installation
OPERATION
The CMB Series relay is used to detect the presence of AC current. When
the monitored current exceeds the trip point for longer than 30 millisec-
onds, the internal relay energizes. When the monitored current drops
below the trip point for longer than 0.5 seconds, the internal relay
de-energizes. The Delay-on-Release is incorporated to prevent nuisance
tripping caused by momentary dips in the load line.
An External CT may be used to extend the range of the Current Monitor.
ORDER INFORMATION
CONTROL VOLTAGE
CURRENT TRIP POINTS
CMB
monitored
protruding Current Transformer
24-A 24 Volts AC
24-D 24 Volts DC
120-A 120 Volts AC
1
3
5
7
9
AC Go/No-Go Current Monitor/Relays
1 amp
3 amps
5 amps
7 amps
9 amps
2
4
6
8
10 10 amps
SERIES
2 amps
4 amps
6 amps
8 amps
CMB-XXX-XFA-XX
SPECIFICATIONS
CATALOG NUMBER:
CONTROL VOLTAGE:
AC INPUT CURRENT:
TRIP POINT:
RESPONSE TIMES
TEMPERATURES
POWER
CONSUMPTION:
OUTPUT:
LIFE EXPECTANCY
DUTY CYCLE:
ENCLOSURE:
SOCKETS:
WIRING
DIMENSIONS
Operate:
Release:
Operate:
Storage:
Mechanical:
Electrical:
INCHES
10 Million Operations (Minimum)
CMB-XXX-AFA-XX
24 or 120 VAC; 50/60 Hz, 24 VDC
Up to 50 Amps
1-10 Amps, Fixed
30 Milliseconds
0.5 Seconds
32° to 131°F (0° to +55°C)
-49° to 185°F (-45° to +85°C)
3 Watts (Approximately)
SPDT, 10 Amps @ 240 VAC Resistive;
211 VA @ 120 VAC Inductive:
1/6 Horsepower @ 120 VAC or 1/3
Horsepower @ 240 VAC
100,000 Operations @ Rated Load
Continuous
Lexan Dust Cover;
8-Pin plug-in
RB-08 or PF083A