SU2200RMXLTNET APC, SU2200RMXLTNET Datasheet - Page 23

no-image

SU2200RMXLTNET

Manufacturer Part Number
SU2200RMXLTNET
Description
UPS - Uninterruptible Power Supplies APC Smart-UPS XL 2200VA RM 5U 208V
Manufacturer
APC
Datasheet

Specifications of SU2200RMXLTNET

Power Rating
1600 W
Output Voltage Rating
208 V
Number Of Outlets
5
Interface Port
DB-9 RS-232, SmartSlot
Runtime (full Load)
10 min
Runtime (half Load)
34 min
Topology
Online
Tower / Rackmount
Rackmount
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
5.2.2 Verifying the Presence of Mounting Holes
1. Examine the rear plate inside the UPS. The configuration of the
5.2.3 Installing the Wire Harness Assembly
NOTE:
mounting holes should appear as in Figure 5-11. If the mounting
and ground screw holes are present in this configuration, proceed
with the installation procedure. If the holes are not present, you
will not be able to install the hardwire kit to this UPS. Contact
your dealer for an alternative solution.
A. Mount the wire harness as instructed (Section 5.2.3), and
B. Retrieve the old line cord and cut the last 6” from the end
If you are hard wiring the input only, choose one of the fol-
lowing two methods:
wire only the Input L1 and Input L2/N connections
or,
with the 4-wire connector attached. This connector and the
attached wires will be spliced to your input line. Using ap-
proved field-applied splicing devices, connect the two black
wires to Line1 (or Hot) of your input line and the two white
wires to Line2 (or Neutral) of your input line. Plug the con-
nector into the mating connector in the UPS (Figure 5-10)
and reinstall the input and output panels.
21