G3NA-425B DC5-24 Omron, G3NA-425B DC5-24 Datasheet - Page 3

RELAY SSR 25A@440VAC ZERO CROSS

G3NA-425B DC5-24

Manufacturer Part Number
G3NA-425B DC5-24
Description
RELAY SSR 25A@440VAC ZERO CROSS
Manufacturer
Omron
Series
G3NAr

Specifications of G3NA-425B DC5-24

Circuit
SPST-NO (1 Form A)
Output Type
AC, Zero Cross
Load Current
25A
Voltage - Input
5 ~ 24VDC
Voltage - Load
180 ~ 528 V
Mounting Type
Chassis Mount
Termination Style
Screw Terminal
Package / Case
Hockey Puck
Control Voltage Range
5 VDC to 24 VDC
Load Voltage Rating
400 V to 600 V
Load Current Rating
25 A
Contact Form
1 Form A
Mounting Style
DIN Rail
Relay Type
General Purpose Hockey Puck
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
On-state Resistance
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
G3NA-425B-DC5-24
G3NA425BDC524
Z170
Specifications
I Input Ratings
(Ambient temperature: 25°C [77°F])
Note: 1. The input impedance is measured at the maximum value of the rated supply voltage (for example, with the model rated at 100 to 120
I Output Ratings
900
G3NA-2❏❏B
G3NA-4❏❏B
G3NA-D210B
G3NA-275B-UTU
G3NA-290B-UTU
G3NA-475B-UTU
G3NA-490B-UTU
G3NA-205B
G3NA-210B
G3NA-410B
G3NA-220B
G3NA-420B
G3NA-240B
G3NA-440B
G3NA-450B
G3NA-D210B
G3NA-275B-UTU 24 to 240 VAC
G3NA-475B-UTU 200 to 480 VAC
G3NA-290B-UTU 24 to 240 VAC
G3NA-490B-UTU 200 to 480 VAC
*When the appropriate size OMRON heat sink is used.
2. With constant current input circuit system, the impedance for the G3NA-2❏❏B-UTU is 15mA max.
3. Refer to the “Characteristic Data” for further details.
Type
Type
VAC, the input impedance is measured at 120 VAC).
Solid State Relay
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 240 VAC
24 to 240 VAC
24 to 240 VAC
200 to 480 VAC
24 to 240 VAC
200 to 480 VAC
24 to 240 VAC
200 to 480 VAC
200 to 480 VAC
5 to 200 VDC
load voltage
voltage
Rated
Rated
G3NA
4 to 32 VDC
75 to 132 VAC
150 to 264 VAC
4 to 32 VDC
75 to 264 VAC
4 to 32 VDC
75 to 264 VAC
19 to 264 VAC
19 to 264 VAC
180 to 528 VAC
19 to 264 VAC
180 to 528 VAC
19 to 264 VAC
180 to 528 VAC
180 to 528 VAC
4 to 220 VDC
19 to 264 VAC
180 to 528 VAC
19 to 264 VAC
180 to 528 VAC
voltage range
voltage range
Operating
Load
7 mA max.
36 kΩ ±20%
72 kΩ ±20%
5 mA max.
72 kΩ ±20%
15 mA max.
72 kΩ ±20%
0.1 to 5 A (at 40°C)
0.1 to 10 A (at 40°C)
0.2 to 10 A (at 40°C)
0.1 to 20 A (at 40°C)
0.2 to 20 A (at 40°C)
0.1 to 40 A (at 40°C)
0.2 to 40 A (at 40°C)
0.2 to 50 A (at 40°C)
0.1 to 10 A (at 40°C)
1 to 75 A (at 40°C)
1 to 75 A (at 40°C)
1 to 90 A (at 40°C)
1 to 90 A (at 40°C)
With heat sink*
(See note 1)
Impedance
Applicable load
(see note 2)
(see note 2)
(see note 2)
Load current
4 VDC max.
75 VAC max.
150 VAC max.
4 VDC max.
75 VAC max.
4 VDC max.
75 VAC max.
0.1 to 3 A (at 40°C)
0.1 to 4 A (at 40°C)
0.2 to 4 A (at 40°C)
0.1 to 4 A (at 40°C)
0.2 to 4 A (at 40°C)
0.1 to 6 A (at 40°C)
0.2 to 6 A (at 40°C)
0.2 to 6 A (at 40°C)
0.1 to 4 A (at 40°C)
1 to 7 A (at 40°C)
1 to 7 A (at 40°C)
1 to 7 A (at 40°C)
1 to 7 A (at 40°C)
Must operate voltage
Without heat sink
(see note 3)
(see note 3)
Voltage level
1 VDC min.
20 VAC min.
40 VAC min.
1 VDC min.
20 VAC min.
1 VDC min.
20 VAC min.
60 A (60 Hz, 1 cycle)
150 A (60 Hz, 1 cycle)
220 A (60 Hz, 1 cycle)
440 A (60 Hz, 1 cycle)
20 A (10 ms)
800 A (60 Hz, 1 cycle)
800 A (60 Hz, 1 cycle)
1,000 A (60 Hz, 1 cycle)
1,000 A (60 Hz, 1 cycle)
Must release voltage
Surge current
(see note 3)
(see note 3)