G3NA-425B DC5-24 Omron, G3NA-425B DC5-24 Datasheet

RELAY SSR 25A@440VAC ZERO CROSS

G3NA-425B DC5-24

Manufacturer Part Number
G3NA-425B DC5-24
Description
RELAY SSR 25A@440VAC ZERO CROSS
Manufacturer
Omron
Series
G3NAr

Specifications of G3NA-425B DC5-24

Circuit
SPST-NO (1 Form A)
Output Type
AC, Zero Cross
Load Current
25A
Voltage - Input
5 ~ 24VDC
Voltage - Load
180 ~ 528 V
Mounting Type
Chassis Mount
Termination Style
Screw Terminal
Package / Case
Hockey Puck
Control Voltage Range
5 VDC to 24 VDC
Load Voltage Rating
400 V to 600 V
Load Current Rating
25 A
Contact Form
1 Form A
Mounting Style
DIN Rail
Relay Type
General Purpose Hockey Puck
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
On-state Resistance
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
G3NA-425B-DC5-24
G3NA425BDC524
Z170
New Models Available at 600 VAC Load
Voltage Line with 10 A, 25 A and 50 A
Output Current
• Load voltage range: 180 to 660 VAC
• Lower input current: 7 mA max at 24 VDC
• All models are same dimensions as G3NA series.
• Built-in varistor effectively absorbs external surges.
• Operation indicator enables monitoring operation.
• Protective cover for greater safety.
• Certified by UL, CSA.
Ordering Information
■ List of Models
Note: 1. The applicable output load depends on the ambient temperature. Refer to Load Current vs. Ambient Temperature in Engineering Data.
■ Accessories (Order Separately)
One-touch Mounting Plates
Heat Sinks
Slim Models Enabling DIN-track Mounting
Photocoupler
R99-12 FOR G3NA
Y92B-N50
Y92B-N100
Y92B-N150
Y92B-P250N
Solid State Relays (600 VAC Models)
G3NA-6
Model
2. Loss time increases under 400 VAC. (Refer to Precautions for Correct Use.) Confirm operation with the actual load.
Isolation
Model
10 A
20 A
40 A
50 A
Yes
Applicable maximum load current
Zero cross
function
Yes
Indicator
10 A at 400 to 600 VAC
25 A at 400 to 600 VAC
50 A at 400 to 600 VAC
Applicable output load
(See note 1.)
Solid State Relays (600 VAC Models)
Low-cost Models
Y92B-A100
Y92B-A150N
Y92B-A250
Model
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 240 VAC
Rated input voltage
20 A
40 A
40 A
Applicable maximum load current
G3NA-610B DC5-24
G3NA-610B AC100-240
G3NA-625B DC5-24
G3NA-625B AC100-240
G3NA-650B DC5-24
G3NA-650B AC100-240
G3NA-6
Model
467

Related parts for G3NA-425B DC5-24

G3NA-425B DC5-24 Summary of contents

Page 1

... Output Current • Load voltage range: 180 to 660 VAC • Lower input current max at 24 VDC • All models are same dimensions as G3NA series. • Built-in varistor effectively absorbs external surges. • Operation indicator enables monitoring operation. • Protective cover for greater safety. ...

Page 2

... VAC max. Applicable load Load voltage range Load current (See note 1.) With heat sink (See note 2.) 0 (at 40°C) 0 (at 40°C) 0 (at 40°C) G3NA-625B-UTU 2 G3NA-6 Voltage level Must release voltage 1 VDC min. 20 VAC min. Inrush current Without heat sink 0 (at 40°C) 150 A (60 Hz, 1 cycle) 0 (at 40° ...

Page 3

... Y92B-N100 Y92B-N150 Y92B-P250N Y92B-A100 Y92B-A150N Y92B-A250 Note: When using a commercially available heat sink, use one with a thermal resistance equal to or less that the OMRON Heat Sink. G3NA-650B 30 25 With standard heat sink (Y92B-N150or Y92B-A150N) 20 With standard heat sink (Y92B-N100 or Y92B-A100) or aluminum plate measuring 15 200 mm x 200 ...

Page 4

... Two screws 58 max. 47.5 44 12±0.4 ■ Optional Accessories (Order Separately) One-touch Mounting Plate The One-touch Mounting Plate is used to mount the G3NA to a DIN Track. R99-12 FOR G3NA (for the G3NA and G3NE) Two, M4 mounting holes for the G3NA 30 Two, M4 mounting ...

Page 5

... Y92B-N150 Heat Sink (for max load current) Type G3NA-625B is recommended for max and G3NA-650B for max with this heat sink. For upright standing to the ground, a 30% derating of the load current is required (from the Load Current vs. Ambient Temperature graphs). The orientation indicated by the external dimensions is not the correct mounting orientation. When opening mounting holes, refer to the mounting hole dimensions ...

Page 6

... Y92B-P250N (for max load current) Type G3NA-650B is recommended for max with this heat sink. For upright standing to the ground, a 30% derating of the load current is required (from the Load Current vs. Ambient Temperature graphs). The orientation indicated by the external dimensions is not the correct mounting orientation. When opening mounting holes, refer to the mounting hole dimensions ...

Page 7

... Y92B-A250 Heat Sink (for max load current) Three, M4 holes 47.6 47.6 R2.2 50±0.1 50±0.1 56±0.5 56±0.5 150 max. 250 max. Weight: approx. 510 g Solid State Relays (600 VAC Models) 102 max. 80.5 max. 1.5 9.6 2 1.5 30 45.5 max. G3NA-6 473 ...

Page 8

... Do not use the G3NA if the heat sink fins are bent, e.g., as the result of dropping the G3NA. Heat dissipation characteristics will be reduced, possibly causing G3NA failure. ...

Page 9

... Operating and Storage Locations Do not use or store the G3NA in the following locations. Doing so may result in damage, malfunction, or deterioration of performance characteristics. • Do not use or store in locations subject to direct sunlight. • Do not use in locations subject to ambient temperatures outside the range −30 to 80°C. ...

Page 10

... Connect the varistor to both sides of the G3NA output terminals. • Do not use an input line that is longer than 3 m. Loss Time The loss time will increase when the G3NA is used at a low applied voltage or current. Be sure that this does not cause any problems. Thickness: 2.3 mm ...

Page 11

... G3NA in locations or by means that will subject it to vibration from other devices, such as motors. 4. Solvents Do not allow the G3NA or the resin portion of the Fan’s thermostat to come in contact with solvents, such as thinners or gasoline. Doing so will dissolve the markings on the G3NA. 5. Oil Do not allow the G3NA terminal cover to come in contact with oil ...

Page 12

... MEMO 478 Solid State Relays (600 VAC Models) G3NA-6 ...

Page 13

... Amendment: These Terms constitute the entire agreement between Buyer and Seller relating to the Products, and no provision may be changed or waived unless in writing signed by the parties. 5. Severability: If any provision hereof is rendered ineffective or invalid, such provision shall not invalidate any other provision. Solid State Relays (600 VAC Models) G3NA-6 ...

Page 14

... European Union's Directive on the Restriction of certain Hazardous Substances ("RoHS"), although the requirements of RoHS do not take effect until July 2006. These requirements may be subject to change. Please consult our website for current information. OMRON ON-LINE Global - http://www.omron.com USA - http://www.components.omron.com Specifications subject to change without notice G3NA-6 Printed in USA ...

Related keywords