H3CR-A AC24-48/DC12-48 Omron, H3CR-A AC24-48/DC12-48 Datasheet - Page 10

RELAY TIMER ANALOG 24VDC/AC

H3CR-A AC24-48/DC12-48

Manufacturer Part Number
H3CR-A AC24-48/DC12-48
Description
RELAY TIMER ANALOG 24VDC/AC
Manufacturer
Omron
Series
H3CR-Ar

Specifications of H3CR-A AC24-48/DC12-48

Mounting Type
Socket
Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
DPDT (2 Form C)
Delay Time
0.05 Sec ~ 300 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 240VAC
Voltage - Supply
24 ~ 48VAC, 12 ~ 48VDC
Termination Style
11 Pin Socketable
Timing Adjustment Method
Hand Dial
Timing Initiate Method
Input Voltage
Time Range
0.05 Sec. To 300 Hr.
Supply Voltage Ac, Min
24VAC
No. Of Timing Functions
6
Body Material
93B4352
No. Of Pins
11
Supply Voltage Ac, Max
48VAC
Load Current Rms Max
5A
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
H3CR-A-AC/DC24
H3CRAAC24-48/DC12-48
H3CRAAC2448DC1248
Z997
H3CR-AP
Voltage Inputs
The start input of the H3CR-AP is voltage input. (Voltage imposition or open)
Note: Before making connections, refer to Safety Precautions (H3CR-
No-contact Input
(Connection to PNP open
collector output sensor)
Sensor
Voltage Input Signal Levels
12 to 24 VDC
(sensor power supply)
No-contact
input
Contact
input
Operates with PNP transistor ON
Use contacts that can adequately switch 0.1 mA at each
operating voltage.
The voltage between terminals 6 and 7 with contacts ON or
OFF must satisfy the specified value.
Contacts ON
100-to-240-VAC and 100-to-125-VDC models: 85 to 264 VAC
or 85 to 137.5 VDC
24-to-48-VAC and 12-to-48-VDC models: 20.4 to 52.8 VAC or
10.8 to 52.8 VDC
Contacts OFF
100-to-240-VAC and 100-to-125-VDC models: 0 to 10 VAC or
0 to 10 VDC
24-to-48-VAC and 12-to-48-VDC models: 0 to 2.4 VAC or 0 to
1.2 VDC
1. Transistor ON
Residual voltage: 1 V max.
The voltage between terminals 6 and 7 must be 10.8 VDC min.
2. Transistor OFF
Leakage current: 0.01 mA max.
The voltage between terminals 6 and 7 must be 1.2 VDC max.
+
2
10
6
7
Timer
DC power
supply
Power
supply (+)
Start
Input 0V
Power
supply
(−)
Note: The input circuit is isolated from the
No-contact Input
(Connection to NPN open
collector output sensor)
Sensor
power supply circuit. Thus, an NPN
transistor can be connected.
12 to 24 VDC
(sensor power supply)
Operates with NPN transistor ON
@
+
).
10
6
7
2
DC power
supply
Timer
Power
supply (+)
Start
Input 0V
Power
supply (−)
Note: Refer to the signal levels in the
Contact Input
Operates with relay ON
following table and be aware of the
minimum applicable load of the relay.
10
6
7
2
Timer
Power
supply (+)
Start
Input 0V
Power
supply (−)
H3CR-A
10