H3CR-A AC24-48/DC12-48 Omron, H3CR-A AC24-48/DC12-48 Datasheet - Page 19

RELAY TIMER ANALOG 24VDC/AC

H3CR-A AC24-48/DC12-48

Manufacturer Part Number
H3CR-A AC24-48/DC12-48
Description
RELAY TIMER ANALOG 24VDC/AC
Manufacturer
Omron
Series
H3CR-Ar

Specifications of H3CR-A AC24-48/DC12-48

Mounting Type
Socket
Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
DPDT (2 Form C)
Delay Time
0.05 Sec ~ 300 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 240VAC
Voltage - Supply
24 ~ 48VAC, 12 ~ 48VDC
Termination Style
11 Pin Socketable
Timing Adjustment Method
Hand Dial
Timing Initiate Method
Input Voltage
Time Range
0.05 Sec. To 300 Hr.
Supply Voltage Ac, Min
24VAC
No. Of Timing Functions
6
Body Material
93B4352
No. Of Pins
11
Supply Voltage Ac, Max
48VAC
Load Current Rms Max
5A
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
H3CR-A-AC/DC24
H3CRAAC24-48/DC12-48
H3CRAAC2448DC1248
Z997
Safety Precautions (H3CR-A)
Refer to Safety Precautions for All Timers.
Note: The following precautions apply to all H3CR-A models.
■ Power Supplies
For the power supply of an input device of the H3CR-A@/-A@S/-AP,
use an isolating transformer with the primary and secondary
windings mutually isolated and the secondary winding not grounded.
The H3CR-A@/-A@S/AP’s power supply terminal 2 is a common ter-
minal for input signals to the Timer. Do not disconnect the wires on
terminal 2, otherwise the internal circuitry of the Timer will be dam-
aged.
Make sure that the voltage is applied within the specified range, oth-
erwise the internal elements of the Timer may be damaged.
Correct
Incorrect
G,
5, 6, 7
S,
G,
Input terminal
Input device
5, 6, 7
R
2
S,
5, 6, 7
G, S, R
Input device
R
2
Input
terminal
H3CR-A
H3CR-A
terminal
Input
transformer
Isolation
10
H3CR-A
2
Isolation transformer is required.
10
2
2
10
Power supply
Power
supply
■ Input/Output
Relationship between Input and Power
Supply Circuits (except for H3CR-A8E)
The H3CR-A (except for H3CR-A8E) uses transformerless power
supply. When connecting a relay or transistor as an external signal
input device, pay attention to the following points to prevent short-
circuiting due to a sneak current to the transformerless power supply.
If a relay or transistor is connected to two or more Timers, the input
terminals of those Timers must be wired properly so that they will not
differ in phase, otherwise the terminals will be short-circuited to one
another.
It is impossible to provide two independent power switches as shown
below regardless of whether or not the Timers are different in phase.
Incorrect
Correct
Contact or transistor for
external input signal
Input
terminal
Input
terminal
Input
terminal
Input
terminal
Input
terminal
Input
terminal
H3CR-A
Short-circuit current
Power supply
H3CR-A
Power supply
Power supply