3UG4513-1BR20 SIEMENS, 3UG4513-1BR20 Datasheet - Page 8

SSR, DIN RAIL, 690VAC, 690VAC, 5A

3UG4513-1BR20

Manufacturer Part Number
3UG4513-1BR20
Description
SSR, DIN RAIL, 690VAC, 690VAC, 5A
Manufacturer
SIEMENS
Datasheet

Specifications of 3UG4513-1BR20

Control Voltage Range
160V To 690V
Operating Voltage Range
200Vrms To 690Vrms
Load Current
5A
Control Voltage Type
AC
Relay Terminals
Screw
Length/height, External
82mm
External Width
22.5mm
Load Voltage Max
400V
Load Current Rms Max
5A
Rohs Compliant
Yes
External Depth
86mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3UG Monitoring Relays for Electrical and Additional Measurements
Voltage monitoring
3UG46 31/3UG46 32 monitoring relays
The 3UG46 31/3UG46 32 voltage monitoring relay is supplied
with an auxiliary voltage of 24 V AC/DC or 24 to 240 V AC/DC
and performs overshoot, undershoot or window monitoring of
the voltage depending on how it is parameterized. The device is
equipped with a display and is parameterized using three
buttons.
The measuring range extends from 0.1 V to 60 V or 10 to 600 V
AC/DC. The threshold values for overshoot or undershoot can
be freely configured within this range. If one of these threshold
values is reached, the output relay responds according to the
set principle of operation as soon as the delay time has elapsed.
This delay time U
The hysteresis is adjustable from 0.1 to 30 V or 0.1 to 300 V.
The device can be operated on the basis of either the open-circuit
or closed-circuit principle and with manual or auto RESET. One
output changeover contact is available as signaling contact.
With the closed-circuit principle selected
Overvoltage
7/68
Monitoring Relays
A1-A2
11/14
11/12
Siemens LV 1 T · 2007
= 0
Del
can be set from 0.1 to 20 s.
>
Delay
Hysteresis
© Siemens AG 2007
Undervoltage
Window monitoring
A1-A2
11/14
11/12
A1-A2
11/14
11/12
= 0
Delay
>
Delay =
Delay
<
<
Delay
Hysteresis
Hysteresis
Hysteresis
Delay

Related parts for 3UG4513-1BR20