T1610000 Red Lion Controls, T1610000 Datasheet - Page 12

Process/Temperature Controller

T1610000

Manufacturer Part Number
T1610000
Description
Process/Temperature Controller
Manufacturer
Red Lion Controls
Type
Temperaturer
Datasheets

Specifications of T1610000

Operating Temperature Max
50°C
Operating Temperature Min
0°C
Output Voltage Max
250VAC
Controller Input
Thermocouple Or RTD
Supply Voltage Max
250VAC
Mounting Type
Panel Mount
Brand/series
T16 Series
Contact Form
SPST
Dimensions
49.5mmW×49.5mmH×115.3mmD
Enclosure Rating
IP65
Input Type
RTD/Thermocouple
Ip Rating
IP65
Memory
EEPROM
Output Type
Relay
Power, Rating
8 VA
Primary Type
Controller
Special Features
EEPROM
Standards
cURus, CE
Termination
Screw
Voltage, Supply
85 to 250 VAC
Thermocouple Type
J, K, T, E, R, S, B, N, C And Linear MV
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
SELECTION
percent function, but is useful in applications that have been scaled in percent.
related parameters.
the nearest rounding increment selected. (For example, rounding of 5 causes 122
to round to 120 and 123 to round to 125.) Rounding starts at the least significant
digit of the process value. Setpoint values, Setpoint limits, Alarm values, Input
Scaling values, and Analog Scaling values are not affected by rounding.
noise and actual process changes. If the signal is varying too greatly due to
measurement noise, increase the filter value. If the fastest controller response is
needed, decrease the filter value.
7.1 MODULE 1 - I
NONE
trnF
F1In
NONE
tYPE
Curr
Select the input type that corresponds to the input signal.
This only illuminates the % annunciator. It does not perform any type of
dCPt
This selection affects the decimal point placement for the Process value, and
Rounding selections other than 1 cause the process value display to round to
FLtr
The filter is an adaptive digital filter that discriminates between measurement
SPt
PCt
rnd
NO
0. 0
0. 1
1
No Function
Auto/Manual Select
Setpoint 1 or 2 Select
0
FUNCTION
0 0. 0 0. 0 0 0. 0 00
1
In steps of 1 least significant digit,
= least to
SELECTION
regardless of decimal point.
to
Curr
VOLt
YES
NO
100
PERCENT ANNUNCIATOR
ROUNDING INCREMENT
DECIMAL RESOLUTION
DIGITAL FILTERING
F1 KEY FUNCTION
Off
On
INPUT TYPE
Current
Voltage
4
SELECTION
A1rS
A2rS
ALrS
TYPE
= most
Reset Alarm 1
Reset Alarm 2
Reset Both Alarms
FUNCTION
NPUT
PARAMETER MENU
P
ARAMETERS
12
while in the Display Loop. In any other loop or module location, pressing
will perform an escape to the Display Loop.
No Function: No function is performed.
Auto/Manual Select: This function toggles (momentary action) the controller
Setpoint 1 or 2 Select: This function toggles (momentary action) the controller
Reset Alarms: This function can be used to reset one or both of the alarms
SCALING
a coordinate pair of Display Values and Input Values. It is recommended that the
two scaling points be at the low and high ends of the input signal being measured.
Process value scaling will be linear between and continue past the entered points
to the limits of the input range. (Factory settings example will display 0.0 at 4.00
mA input and display 100.0 at 20.00 mA input.) Reverse acting indication can be
accomplished by reversing the two signal points or the Display value points, but
not both. If both are reversed, forward (normal) acting indication will occur. In
either case, do not reverse the input wires to change the action.
keys. To allow the P16 to “learn” the signal, use the Applied Method. For Applied
Method, press
Adjust the applied signal level externally until the appropriate value appears
under INP1. Using either method, press
controller can be toggled back to the Key-in Method by pressing
100. 0
The controller performs the selected F1 Key Function, when
between Automatic and Manual Control.
between Setpoint 1 and Setpoint 2.
when activated (momentary action) The alarm will remain reset until the
alarm condition is cleared and triggered again.
To scale the controller, two scaling points are necessary. Each scaling point has
dSP1
Enter the first coordinate Display Value by using the arrow keys.
INP1
For Key-in Method, enter the first coordinate Input Value by using the arrow
dSP2
Enter the second coordinate Display Value by using the arrow keys.
4. 0 0
0. 0
(
-999
0. 0 0
0. 0 0
-999
. The ° annunciator is turned on to indicate the applied method.
DISPLAY VALUE SCALING POINT 1
DISPLAY VALUE SCALING POINT 2
INPUT VALUE SCALING POINT 1
) P16 O
to
to
to
to
20. 0 0
10. 0 0
9999
9999
mA
V
NLY
to store the value for INP1. (The
before
is pressed
.)