T1610000 Red Lion Controls, T1610000 Datasheet - Page 6

Process/Temperature Controller

T1610000

Manufacturer Part Number
T1610000
Description
Process/Temperature Controller
Manufacturer
Red Lion Controls
Type
Temperaturer
Datasheets

Specifications of T1610000

Operating Temperature Max
50°C
Operating Temperature Min
0°C
Output Voltage Max
250VAC
Controller Input
Thermocouple Or RTD
Supply Voltage Max
250VAC
Mounting Type
Panel Mount
Brand/series
T16 Series
Contact Form
SPST
Dimensions
49.5mmW×49.5mmH×115.3mmD
Enclosure Rating
IP65
Input Type
RTD/Thermocouple
Ip Rating
IP65
Memory
EEPROM
Output Type
Relay
Power, Rating
8 VA
Primary Type
Controller
Special Features
EEPROM
Standards
cURus, CE
Termination
Screw
Voltage, Supply
85 to 250 VAC
Thermocouple Type
J, K, T, E, R, S, B, N, C And Linear MV
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
WIRING CONNECTIONS
controller, use the numbers on the label and those embossed on the back of the
case, to identify the position number with the proper function.
Also, cabling should conform to appropriate standards of good installation, local
CONTROLLER POWER CONNECTIONS
the specified limits. Drawing power from heavily loaded circuits or
from circuits that also power loads that cycle on and off should be
avoided. It is recommended that power supplied to the controller be
protected by a fuse or circuit breaker.
INPUT CONNECTIONS
as the RTD leads. Attach one end of the wire at the probe and the other end to
input common terminal. Complete lead wire compensation is obtained. This is
CONTROL AND ALARM OUTPUT CONNECTIONS
3.0 W
All wiring connections are made to the rear screw terminals. When wiring the
All conductors should meet voltage and current ratings for each terminal.
For best results, the power should be relatively “clean” and within
For two wire RTDs, install a copper sense lead of the same gauge and length
RTD and Resistance
ANALOG DC OUTPUT CONNECTIONS
*A1 becomes main control O1, if selected for
heating in the analog out models.
IRING THE
Alarm Models
C
ONTROLLER
Thermocouple and Millivolt
6
codes and regulations. It is recommended that power (AC or DC) supplied to the
controller be protected by a fuse or circuit breaker. Strip the wire, leaving
approximately 1/4" (6 mm) bare wire exposed (stranded wires should be tinned
with solder). Insert the wire under the clamping washer and tighten the screw
until the wire is clamped tightly.
the preferred method. If a sense wire is not used, then use a jumper. A
temperature offset error will exist. The error may be compensated by
programming a temperature offset.
VDC
USER INPUT CONNECTIONS
Main Control Relay Models
Main Control Logic/SSR Models
Voltage and Current
VAC