3-2
3-2-1
Setting the Routing Tables
Routing Table Setting Example
PLC1
PLC2
PLC3
This section explains how to make the necessary settings when transferring the FINS
local routing tables to a PLC connected directly by a serial connection.
This section explains how to create and transfer the FINS local routing tables for the
following network structure.
Example: Routing from PLC1 to PLC3
All of the following routing tables must be created and transferred for this example
network.
Transfer routing
table required in
PLC1.
To go to network address 2, it is necessary to
go to node address 3 in network address 1.
Go through unit number 0 to send to
network address 1.
Local Network Table
Relay Network Table
Local Network Table
Local Network Table
Relay Network Table
PLC1 Relay Network Table
PLC1 Local Network Table
Local node PLC1
Node address 1
(Unit number 0)
Destination
Unit number
address
network
Destination network
Destination network
2
0
Unit number
Unit number
Unit number
address
address
0
4
5
0
Relay network
2
1
Local network address
address
Network address 1
1
1
Relay node
address
Local network address
Local network address
Local network address
3
Relay node PLC2
Node address 3
(Unit number 4)
Relay network address
Relay network address
Transfer routing
table required in
PLC2.
Go through unit number 5 to send to network
address 2.
PLC2 Local Network Table
1
1
2
2
Unit number
1
2
4
5
Node address 1
(Unit number 5)
Network address 2
Local network address
3-2-1 Routing Table Setting Example
1
2
3-2 Setting the Routing Tables
Relay node
Relay node
address
address
3
1
Node address 2 (Unit number 0)
Transfer routing
table required in
PLC3.
Target node PLC3
Shows that communications frames from
network address 2 go to unit number 0.
The communications result must be returned to
PLC1 as a response. To go to network address
1, first it is necessary to go to unit number 0 in
network address 2.
PLC3 Local Network Table
PLC3 Relay Network Table
Destination
Unit number
network
address
1
0
Relay network
Local network address
address
Send to node address 2 in
network address 2 to send
to target node.
2
2
Relay node
address
1
3-11