The local network table can also be set using the following procedure.
1. Click the Main View Tab and select Edit – Add SIOU.
2. The Enter SIOU Details Dialog Box will be displayed.
Creating the Serial Port's Local Network Table:
A local network table can be created for the serial port in the CPU Unit or a Serial
Communications Board or Unit (Version 1.2 or later) so that the serial port can be
specified instead of the Communication Unit's unit number. Creating the local network
table allows the serial port to be managed in the network.
Example 1:
When an NS-series PT is connected to a serial port on the CPU Unit, the PT's screen
data can be transferred from CX-Designer through Ethernet.
Note: In order to transfer screen data through the PLC, the PLC must be a CS/CJ-series PLC
Example 2:
The serial gateway to Host Link FINS can be used across networks.
1. Click the SIOU Tab in the PLC Routing Table Window.
2. The following steps show how to set the local network table for each serial port.
Input the CPU SIOU (unit number) and local network address.
The local network table will be added to the PLC Routing Table Window (Main
View).
The CPU Unit's serial port and the serial ports of Serial Communications
Boards/Units (Unit version 1.2 or later) will be displayed in the directory tree.
Serial Communications Board or Unit:
For a Serial Communications Unit, right-click the Port 1 or Port 2 Icon below the
unit number and select Insert PORT. For a Serial Communications Board,
right-click the Port 1 or Port 2 Icon below unit 225 and select Insert PORT.
with a CPU lot number of 030201 (manufactured February 1, 2003) or later. In addition,
the CPU Unit must be a CS1G-H, CS1H-H, CS1D-S, CJ1M, CJ1G-H, or CJ1H-H. (The
screen data cannot be transferred through a CS1D-H).
Input the unit number.
Input the local network
address.
3-2-2 Creating the FINS Local Routing Tables
3-2 Setting the Routing Tables
3-15