30177 GAMEWELL-FCI [Gamewell-FCI by Honeywell], 30177 Datasheet

no-image

30177

Manufacturer Part Number
30177
Description
Analog Addressable Control Panel with Voice Evacuation
Manufacturer
GAMEWELL-FCI [Gamewell-FCI by Honeywell]
Datasheet
©2007 Honeywell International Inc. All rights reserved.
Description
The IdentiFlex 602 with Voice Evacuation (IF602VE) is ide-
ally suited for small- to medium-sized installations of com-
mercial, institutional, and industrial life-safety applications.
The IF602VE offers all the features of today’s most
advanced life safety systems. The integration of analog
and addressable hardwired circuits allows system engi-
neers to customize panels and maximize efficiency for a
given application.
The IF602VE can monitor and control up to 252 intelligent
analog addressable input/output points. The interactive
operator’s display uses LED prompting for ease of pro-
gramming and user operation. The alphanumeric display
and keypad simplify field programming, or download pro-
gramming from a Windows
State-of-the-art, single-channel (25 watts) voice evacuation
is built into the IF602VE panel. It is expandable to 50 watts.
With zone splitting, up to 50 watts of audio power can be
divided into as many as eight speaker circuits (zones), and
full manual control with status indication is included via a
separate keypad.
With the IF602VE, up to five field-programmable messages
(up to 60 seconds total message duration) can be recorded
with an integral microphone or from an external audio
source. The panel provides full supervision in both active
alarm and standby conditions; the amplifier outputs, field
wiring, message generator, all tone generators, and the
microphone are all supervised.
The IF602VE’s housing was designed to be both aestheti-
cally pleasing and functionally sound. The cabinet is
designed to fit between studs for semi-flush mounting. The
compact design and key-activated dead-front construction
enables secure routine maintenance of the system. Access
to system function keys is limited by a key switch. Multiple
levels of password protection prohibit unauthorized use.
The circuit boards are mounted on a removable chassis,
and are designed with pluggable terminal strips for ease of
installation and service.
SmartStart™ and SmartLink™ are trademarks of Honeywell International Inc.
Microsoft
®
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
Windows
®
is a registered trademark of Microsoft Corporation.
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
®
-based application.
www.gamewell-fci.com
GAMEWELL-FCI
Feature
• One or two Signaling Line Circuits (SLC), up to 252
• Polarity-insensitive SLC circuit wiring.
• SmartStart™ self-programming logic.
• Downloadable or front-panel programmable.
• Password protected.
• Approved for Agent Releasing and Supervisory Service.
• Fully digital SLC protocol.
• SmartLink™ peer-to-peer networkable.
• 1000-event history log.
• Automatic drift compensation.
• Coded signaling capability.
• Adjustable sensor sensitivity and temperature settings.
• Supervisory service.
• Style 6 (Class A) or Style 4 (Class B) SLC.
• Four Style Y (Class B), or two Style Z (Class A)
• Semi-flush mounting (between 16" studs).
• 160-character display.
• UDACT compatible.
• Built-in strobe and horn synchronization.
points.
notification appliance circuits (NACs).
Analog Addressable Control Panel
IdentiFlex 602VE
An ISO 9000-2000 Company
SIGNALING
with Voice Evacuation
600 Series
S521
IF602VE
CS-2497 Rev. A page 1 of 4
APPROVED
FM

Related parts for 30177

30177 Summary of contents

Page 1

Description The IdentiFlex 602 with Voice Evacuation (IF602VE) is ide- ally suited for small- to medium-sized installations of com- mercial, institutional, and industrial life-safety applications. The IF602VE offers all the features of today’s most advanced life safety systems. The integration ...

Page 2

Operator’s Display The IF602VE’s operator’s display is the source of all user access to the system. The display provides all of the nec- essary keys and annunciation points to maintain and moni- tor the system. Alarm, supervisory, and trouble conditions ...

Page 3

... Model IF602VE-126 IF602VE-252 IF602VE-126Z IF602 analog addressable system, con- IF602VE-252Z • IF602 analog addressable system, 252 0.055A 0.055A 52286 30177 31078 GAMEWELL-FCI www.gamewell-fci.com Description IF602 analog addressable system, con- sisting of the following: • IF602 common control. • 8.0 amp main power supply. ...

Page 4

Ordering Information (Continued) Model Description 31079 CLA-602, Class “A” adapter module for SLC, 602 Series panels. Audio Subsystem: ACC-AAM25 Optional 25 watt Module with single Class A or Class B speaker circuit. FC-XRM70 Optional 70.7 V RMS (one ...