Application Example: 50-watt zone splitting, eight speaker circuits
50 watts total power with automatic control via ACS link from the FACP — see diagram below.
This application of the GWACCZ configures the zone splitter module (ACC-ZSM) to divide 50 watts of audio from two audio
amplifiers (ACC-AAM25) into four speaker circuits each. The FACP uses the ACS link connected to the zone page module
with keypad (ACC-ZPMK) for automatic activation of the speaker zones and for alarm activation.
Configuration switches are set as follows:
• ACC-ZSM SW1 set to “AAM1 & AAM2” and SW2 to “Class B” to place speaker circuits 1 – 4 on AAM1
• ACC-ZPMK DIP switch S1 set for communication with software version 2.x (1 = ON, 2 = OFF, 3 = OFF).
• GWACCZ main circuit board DIP switch S3 set for single zone mode, All-Call and two messages
The FACP can automatically activate the Fire Evacuation Message and any combination of the eight speaker zones. For
speaker circuit manual deactivation, press the activated zone pushbutton on the ACC-ZPMK keypad. For manual activa-
tion, press either of the Message push-buttons, then select the Zone pushbutton on the ACC-ZPMK keypad. For All-Call
Paging, press the All-Call pushbutton on the main panel keypad, then key the microphone to make an announcement.
GWACCZ CS-2505 09/01/06
and speaker circuits 5 – 8 on AAM2, configured for Style Y (Class B) wiring.
(1 = ON, 2 = OFF, 3 = OFF).