EDS11-102E FUJI [Fuji Electric], EDS11-102E Datasheet

no-image

EDS11-102E

Manufacturer Part Number
EDS11-102E
Description
FC SERIES COMPACT CONTROLLER S(PROGRAMMABLE, STEP OUTPUT TYPE)
Manufacturer
FUJI [Fuji Electric]
Datasheet
FEATURES
1. Abundant control and computation functions
2. Control and computation programming can be made
3. High reliability
FUNCTIONAL DIAGRAM
pact single-loop controller using a microprocessor. It accepts
uniform signal, and signals from thermocouple and RTD
(Resistance bulb) as input, and is equipped with abundant
control and computation functions to allow composing a flex-
ible system with a high cost/performance.
DATA SHEET
The controller has a variety of control and computation
functions in addition to PID auto tuning, and also has a
transmission function for data exchange with a host sys-
tem.
at the site
Since the control and computation functions are built into
wafers (functional units), an optimum program for the con-
trol object can be formed just by keying on the front panel.
LED's (red and green) are used for the bargraph indicator
and also for the parameter indication (red), and a non-
volatile memory enables retaining the control and com-
putation parameters even if power should be interrupted.
The Compact Controller S (programmable type) is a com-
Manual mode command (SMV)
FC SERIES COMPACT CONTROLLER S
(PROGRAMMABLE, STEP OUTPUT TYPE)
External set point input
Auxiliary analog input 1
Auxiliary analog input 2
Process variable input
Auxiliary digital input 1
Auxiliary digital input 2
Auxiliary digital input 3
Pulse width input (PI+)
Pulse width input (PI-)
Valve opening input
(Resistance) (W)
(CAS)
(DI1)
(DI2)
(DI3)
(AI1)
(AI2)
(PV)
Resistance
input converter
4 to 20mA,
thermocouple
RTD
conversion
Communication
terminals
up to 24 wafers
usable
KPV
SV
Serial communication interface
PV
SV
Personal computer
SUB control block
(cascade control, ratio
Computation wafer
MAIn control
block (basic control)
control or schedule
control)
Fault
Control wafer
Control wafer
Constant
Manual
1
Alarm
4. All operation is made from the front panel
5. Personal computer interface
Constant
32
Operations such as parameter setting, auto/manual
changeover are all made from the front panel.
Generic interface availability for personal computer (IBM
PC-AT) for supervision, operation, support, maintenance,
etc.
MV
Bargraph
indicator
FLT Indictor
H Indictor
L Indictor
Other controllers
Manual mode output
Auxiliary analog output 1
Compensated PV signal (KPV)
Set point transmit signal (SV)
Manipulated output (Pulse width)
Auxiliary digital output 1
Auxiliary digital output 2
High alarm (H)
Low alarm (L)
Fault output
(FLT)
(M)
(DO1)
(DO2)
(AO1)
(PO)
Date
EDS11-102e
PNC2
Jan. 27, 1999

Related parts for EDS11-102E

EDS11-102E Summary of contents

Page 1

... Manipulated output (Pulse width) Control wafer MV SV Auxiliary digital output 1 Auxiliary digital output 2 Computation wafer High alarm (H) Low alarm (L) Manual mode output Manual Fault FLT Indictor H Indictor Alarm wafers L Indictor usable PNC2 (AO1) (PO) (DO1) (DO2) (M) Fault output (FLT) EDS11-102e Date Jan. 27, 1999 ...

Page 2

PNC2 SPECIFICATIONS 1. Control functions (1) PID control: Proportional band (P); 1.0 to 3276.7% Integration time (I); 0.1 to 3276.7 sec Derivative time (D); 0.0 to 900.0 sec PID auto tuning function (according to Wafer system program: The following kinds ...

Page 3

Input signals (1) Process variable input signal: One input selectable from the following Voltage input Input resistance 1M signal more Allowable error 0.2%/FS* Current input 4 to 20mA DC 24V DC can be supplied to ...

Page 4

PNC2 7. Power failure processing function Power failure detection: Control stoppage at power failure detec- tion During power failure: Operating parameters backed up by ca- pacitor when power failure within 5 min- utes. Initial set point and manipulated output values, ...

Page 5

Operating conditions Power supply: Selectable from the following 3 types 24V DC (20 to 30V DC), 100V AC (85 to 132V/47 to 63Hz AC), 200V AC (187 to 264V/47 to 63Hz AC) Power consumption: Approx. 12W (DC), 20VA (AC) ...

Page 6

PNC2 Ratio control Ratio control is carried out by combining a ratio computation block and a PID control block. Program control By combining a program set- ting block and a PID control block, the set point is changed and controlled ...

Page 7

EXTERNAL CONNECTION DIAGRAM Block terminals (M4 screw) Process variable I+ 11 input (PV (SC) PI Manual mode) PI Aux. digital output) FLT 34 DO SMV 15 Manual ...

Page 8

PNC2 OUTLINE DIAGRAM (Unit:mm) Terminals Panel thickness 8 or less Terminal cover Supporting bracket 140 36 355 TRANSMISSION CONNECTOR SIG GND 1 (VST SHLD 7 3 INH 8 RXD+ 4 TXD+ 9 RXD– 5 TXD– YELLOW GREEN BROWN ...