EDS11-102E FUJI [Fuji Electric], EDS11-102E Datasheet - Page 4

no-image

EDS11-102E

Manufacturer Part Number
EDS11-102E
Description
FC SERIES COMPACT CONTROLLER S(PROGRAMMABLE, STEP OUTPUT TYPE)
Manufacturer
FUJI [Fuji Electric]
Datasheet
4
7. Power failure processing function
Power failure detection:
During power failure:
Power failure recovery time:
*Control mode at initialization is settable.
8. Self-diagnosis functions
Computation/control circuit abnormality:
Input/output signal abnormality, manipulated output
deisconnection: FLT indicator lights up, FLT contact out-
Fault contents indication:
9. Transmission functions
(1) Transmission items
Setting operation items:
(2) Transmission setting inhibit:
PNC2
M: Manual mode
A: Automatic mode
R: Remote mode
SCC: SCC mode
Supervisory items:
Parameter setting enable/inhibit can be designated by
transmission from the host. Designation is done by F/S ,
,
,
, ST keys on the front panel.
Control stoppage at power failure detec-
tion
Operating parameters backed up by ca-
pacitor when power failure within 5 min-
utes.
Initial set point and manipulated output
values, PID parameters etc. are stored in
nonvolatile memory (lasts for 10 years or
longer at ambient temperature of 50 C or
less).
Initial or continuous start settable for
power failure within 5 minutes. Recovery
from power failure lasting longer than 5
minutes is done by initial.
FLT indicator lights up, FLT contact out-
put turns ON, and computation and con-
trol stop.
Manipulated output can be controlled
manually at FLT (Soft manual).
put turns ON, control stops, and manipu-
lated output is held. Computation proc-
essing and output processing other than
for manipulated output continue.
Cause of fault is indicated numerically on
numerical indicator of front panel.
From PNA to host
Process variable, set point, manipulated
output, deviation, operation mode, alarm
information, fault information, PID para-
meters, various limiter values, constants,
segmented line, analog input/output, digi-
tal input/output, control program (Wafer
connecting information) etc.
From host to PNA
Set point, manipulated output, operation
mode, PID parameters, various limiter
values, constants, segmented line, con-
trol program (Wafer connecting informa-
tion) etc.
(3) Transmission interface
10. Other functions
CODE SYMBOLS
P N C 2
1 2 3 4 5 6 7 8
CC data line or RS-422 interface selectable
CC data line: Connected with transmission controller
Interface:
Transmission speed:
No. of units connectable:
Transmission distance:
Transmission form:
Cord format: 12 bit binary
RS-422:
Transmission speed:
No. of units connectable:
Transmission distance:
Code format: One or two stop bits, parity EVEN/ODD/
Data protective function by means of pass code
W
D
G
A
B
C
E
F
A
B
1
2
3
5 -
1
2
9 10 11 12
(PMN)
PMN and PNC; CC data line
(RS-232C for PMN and host)
19.2 KBPS
15 max.
500m max.
Multi-drop
Universal interface
2400, 4800, 9600 or 19200 BPS con-
figurable
31 max.
1km max.
NONE configurable.
R
C
0
1
Note: Symbols of resistance bulbs are as
A
Y
Process variable input signal
1 to 5V DC
4 to 20mA DC
J thermocouple
K thermocouple
E thermocouple
R thermocouple
Resistance bulb JPt100 (0 C)
Resistance bulb Pt100 (0 C)
Setting method
A-M type
R-A-M type
Power supply
24V DC (20 to 30V DC)
110V AC (85 to 132V AC) 50/60Hz
220V AC (187 to 264V AC) 50/60Hz
Valve opening input
1 to 5V DC
10-100-10
Transmission function
RS-422
CC data line
Wafer connection
Without
With
PID auto tuning function
Without
With
follows.
JPt100 ..... JIS C 1604-1981
Pt100 ..... IEC Pub751-1983
3-wire type, 50 C span or more
3-wire type, 50 C span or more
Description
(Approx. 24V DC
10mV DC span or
more, with refer-
ence junction com-
pensating function
supply)

Related parts for EDS11-102E