EDS11-106E FUJI [Fuji Electric], EDS11-106E Datasheet - Page 3

no-image

EDS11-106E

Manufacturer Part Number
EDS11-106E
Description
FC SERIES RATIO SETTER
Manufacturer
FUJI [Fuji Electric]
Datasheet
Power failure recovery:
6. Self-diagnosis functions
Computing circuit abnormality:
Input/output signal abnormality:
Fault contents indication:
7. Transmission functions
(1) Transmission items
Setting operation items:
(2) Transmission setting inhibit:
(3) Communication interface
(a) T-link: Private interface
(b) RS-422A/485: Universal interface
(c) CC data line: Private interface
8. Other functions
Data protective function by pass code
9. Operating conditions
Power supply:
Power consumption:
Supervisory items:
Parameter setting enable/inhibit can be designated by
transmission from the host. Designation is done by keys
on the front panel.
Transmission speed: 500Kbps
No. of units connectable: 32 max.
Transmission distance: 1km max.
Transmission form: Multi-drop
Control method: I/O transmission and message
Transmission speed: 2400, 4800, 9600 or 19200bps
No. of units connectable: 31 max.
Transmission distance: 1km max.
Transmission form: Multi-drop
Control method: Polling/selecting
Transmission speed: 19.2Kbps (fixed)
No. of units connectable: 15 max.
Transmission distance: 500m max.
Transmission form: Multi-drop
Control method: Polling/selecting
Initial or continuous start mode can be
set within 5 minutes of power failure.
Recovery from power failure lasting
longer than 5 minutes is done by initial.
Note: ** Control mode at initialzation can be
FLT lamp lights, FLT contact output "ON".
Manual operation output possible
FLT lamp lights, FLT contact output "ON",
computation stops, operating output held
Cause of fault is indicated numerically on
numerical indicator on front panel
PNG
Process value, set point, control output,
operation mode, alarm information, fault
information, various limiter values,
constants, etc.
Host
Set point, control output, operation mode,
various limiter values, constants, etc.
Select from 3 types
24V DC (20 to 30V DC)
100V AC (85 to 132/47 to 63Hz AC)
200V AC (187 to 264V/47 to 63Hz AC)
Approx. 11W (DC)
Approx. 20VA (AC)
L: Local mode or R: Remote mode
configurable
registered
host
PNG
Dielectric strength:
Insulation resistance:
Ambient temperature:
Ambient humidity:
Enclosure:
Rating plate (Name plate):
Dimensions:
Mass {weight}:
Mounting method:
Finish color:
Scope of delivery: Setter and mounting bracket
Item to be ordered separately:
CODE SYMBOLS
1 2 3 4 5 6 7 8
P N G 1
W
D
G
A
B
C
E
F
A
B
1
2
3
5 -
9
0
10
Note: Symbols for resistance bulb are as follows.
1500V AC, 1 min.
500V DC, 100M
0 to 50 C
90% RH or less
Steel case
100 (H) x 70 (W) mm, white acryl
144 (H) x 72 (W) x 391 (D) mm, IEC
(DIN) standard
Flush with indoor mounting; vertical
mounting.
Mountable on tilted surface, angle " "
Munsell N 1.5 for both front panel and
case
Communication cable (type PNZ)
Y
T
R
S
C
Approx. 2.9kg
Process value input signal
1 to 5V DC
4 to 20mA DC
J thermocouple
K thermocouple
E thermocouple
R thermocouple
Resistance bulb, JPt 100, 3-wire, 50 C
span or more
Resitance bulb, Pt100, 3-wire, 50 C
span or more
Setting method
L type
R-L type
Power supply
24V DC (20 to 30V DC)
100V AC (85 to 132V/47 to 63Hz AC)
200V AC (187 to 264V/47 to 63Hz AC)
Transmission function
None
T-link
RS-422A
RS-485
CC data line
JPt100.....JIS C 1604-1981
Pt100.....IEC Pub 751-1983
(Selection of JPt100/Pt100 possible by front
key operation)
=0 to 90
Description
or more
10mV DC span or
more, with cold
junction compen-
sation
3