DS1200-3-002 Emerson Network Power, DS1200-3-002 Datasheet - Page 51

no-image

DS1200-3-002

Manufacturer Part Number
DS1200-3-002
Description
POWER SUPPLY AC/DC 12V 1200W
Manufacturer
Emerson Network Power
Series
DS1200r
Datasheets

Specifications of DS1200-3-002

Voltage - Output
12V
Number Of Outputs
1
Power (watts)
1200W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
180 ~ 264VAC
Mounting Type
Chassis Mount
1st Output
12 VDC @ 100A
Size / Dimension
11" L x 3.2" W x 1.57" H (279.4mm x 81.3mm x 39.9mm)
Power (watts) - Rated
1200W
Operating Temperature
-10°C ~ 50°C
Efficiency
91%
Approvals
CB, CE, cUL, EN, NEMKO, UL
Line Regulation
±5%
Load Regulation
±5%
Input Voltage
90 to 264V
Output Voltage
12V
Input Frequency
47 to 63Hz
Screening Level
Commercial
Operating Temperature Min Deg. C
-10C
Operating Temperature Max Deg. C
50C
Mounting Style
Desktop
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
454-1271
DS1200-3 Series Supported PMBus
Command
Code
3Ah
3Bh
4Ah
4Fh
5Ah
5Bh
40h
41h
42h
43h
44h
45h
46h
47h
50h
51h
55h
56h
57h
58h
59h
Command Name
FAN_ CONFIG_1_2
b7
b6
b5:4
b3
b2
b1:0
FAN_COMMAND_1
VOUT_OV_FAULT_LIMIT
VOUT_OV_FAULT_RESPONSE
VOUT_OV_WARN_LIMIT
VOUT_UV_WARN_LIMIT
VOUT_UV_FAULT_LIMIT
VOUT_UV_FAULT_RESPONSE
IOUT_OC_FAULT_LIMIT
IOUT_OC_FAULT_RESPONSE
IOUT_OC_WARN_LIMIT
OT_FAULT_LIMIT
OT_FAULT_RESPONSE
OT_WARN_LIMIT
VIN_OV_FAULT_LIMIT
VIN_OV_FAULT_RESPONSE
VIN_OV_WARN_LIMIT
VIN_UV_WARN_LIMIT
VIN_UV_FAULT_LIMIT
VIN_UV_FAULT_RESPONSE
IIN_OC_FAULT_LIMIT
TM
Command List:
Default Value
D430 High
C02B high
4826 Low
6022 Low
FC03
90EA
80EA
4C04
A816
70E3
26FA
26FA
40D3
6400
6405
1405
C0
90
01
00
80
80
B8
00
00
1
0
0
0
Access
Type
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Bytes
Data
1
2
2
1
2
2
2
1
2
1
2
2
1
2
2
1
2
2
2
1
2
Format
Linear
Linear
Linear
Linear
Linear
Direct
Direct
Direct
Direct
Direct
Direct
Direct
Direct
Direct
Data
Used to configure up to 2 fans associated with
one PMBus device
1 – Fan is installed in position 1
0 – No Fan is installed in position 1
1 – Fan is commanded in RPM
0 – Fan is commanded in DC
00 – 1 pulse per revolution
01 – 2 pulses per revolution
10 – 3 pulses per revolution
11 – 4 pulses per revolution
1 – Fan is installed in position 2
0 – No Fan is installed in position 2
1 – Fan is commanded in RPM
0 – Fan is commanded in DC
00 – 1 pulse per revolution
01 – 2 pulses per revolution
10 – 3 pulses per revolution
11 – 4 pulses per revolution
Adjusts the operation of the Fans. The device
may override the command, if it requires higher
value, to maintain proper device temperature.
RPM Control – Commands Speeds from 0-
65535 RPM.
Duty cycle Control – Commands Speeds from 0
to 100%
Sets Output Over voltage threshold. (13.8V)
Unit Latches OFF. Resets on PSON or
CONTROL pin recycle or AC recycle.
Sets Over-voltage Warning threshold. (13V)
Sets Under-voltage Warning threshold. (11V)
Sets Under-voltage Fault threshold. (10.2V)
Turn PSU OFF
Sets the Over current threshold in Amps. (125A
for Hi Line and 98A for Low Line)
OCP ride through. If OCP persists.
Sets the Over Current Warning threshold in
Amps. (112A for Hi Line and 88A for Low Line)
Secondary ambient temperature Fault threshold,
in degree C. (58degC)
Turn PSU OFF and will retry indefinitely
Secondary ambient temperature warning
threshold, in degree C. Operating limit. refer to
section 3.1. (55 degC)
Sets input over-voltage threshold. (275Vac)
No interruption.
Sets the threshold of input voltage that triggers
high voltage warning. (275Vac)
(82Vac)
(80Vac)
Sets the threshold for input current that causes
over-current fault within 100ms. (13A)
Description
Rev.10.03.30_#0.1
DS1200-3 Series