RP-RM83F-38LR BANNER ENGINEERING, RP-RM83F-38LR Datasheet - Page 6

no-image

RP-RM83F-38LR

Manufacturer Part Number
RP-RM83F-38LR
Description
Heavy-Duty Emergency Stop Rope Pull
Manufacturer
BANNER ENGINEERING
Type
Safetyr
Datasheet

Specifications of RP-RM83F-38LR

Ring Attachment
38 Meter Max. Range
Actuator Type
Latch
Body Style
Rectangular
Current, Rating
50 mA
Ip Rating
IP67
Number Of Positions
2
Voltage, Rating
10-30 VDC
Lead Free Status / Rohs Status
RoHS Compliant part
6
P/N 141245 rev. A 01/09
RP-RM83F-.. Heavy-Duty Rope Pulls
Access to Wiring Chamber
Access the wiring chamber by loosening the 4 corner screws to remove the front cover. Select the best wiring
entrance and thread in the ½" x 14 NPSM conduit adapter (supplied), or the optional M20 x 1.5 cable gland
(see Accessories).
Figure 5: Wire the two switch contacts in series or independently, as described below
Wiring
These switch models have redundant pairs of safety contacts, so they may be wired for either single-channel
or dual-channel output to a safety module or E-stop circuit. Monitor contacts may be wired as desired to an
external alarm device.
Single-Channel Output: Wire both 11/12 contacts in series to the input of a safety module or E-stop circuit.
Dual-Channel Output: Wire both 11/12 contacts independently to the two safety module inputs.
"Warning Signal"
Maximum tightening torque of contact screws is specified at 0.8 Nm; do not over-tighten. Before closing the front
cover, verify that no wires are trapped. Do not operate the rope pull without properly closing the cover.
Switch models RP-RM83F-...E provide a 24V dc solid-state
“warning signal” output, that signals when the rope tension
is either too high or too low, before the safety contacts
open and the switch latches OFF. This solid-state switch
is located inside the wiring chamber next to the safety
output contacts.
Single-Channel Connection
CAUTION . . . Proper Wiring
11
23
10-30 VDC
12
24
Banner Engineering Corp. - Minneapolis, MN U.S.A. - www.bannerengineering.com - Tel: 763.544.3164
1
2
3
Load
+
1
2
3
11
23
12
24
PNP
Warning Signal
Connections
Electrical Installation
Figure 6: Warning signal electrical connections
Channel A
Dual-Channel Connection
11
23
10-30 VDC
12
24
1
2
3
Load
1
2
3
+
1
2
3
11
23
12
24
Load
Channel B
+
0V-DC
+24V
1
2
3

Related parts for RP-RM83F-38LR