Specifications of CV500CN228

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
PC Switch Settings
When the PT and PC are connected together, set the conditions at the PC Host Link Unit and the CPU as shown in
the table below.
The method of setting the conditions with the switches on each unit is described on the following pages. Refer to
the manual on each unit for more detailed information on making these settings.
Note The 1-to-N setting enables BCC (Block Check Character). The 1-to-N connection cannot be used to con-
Connection to a Host Link Unit
Two types of Host Link Unit are available: a Rack-mounting type and a CPU-mounted type. The switch settings
differ according to the type of Host Link Unit. Set the switches according to the unit type.
C200H: Rack-mounting Type
C200H-LK201
C200H-LK202
C200H-LK101-P
Setting the Front Switches
Set each switch with a flathead screwdriver until the displayed settings agree with the settings described on the
previous page.
I/O port
Baud rate
Transfer code
Parity
1-to-1/1-to-N
Instruction level
Unit#
nect a Host Link Unit to a PT.
SW1
SW3
RUN
RCV
LK101
Item
0
5
0
2
ERROR
XMT
SW2
SW4
SW1/SW2: Set the Unit#
SW4: Sets the instruction level, parity, and transfer code.
SW3: Baud rate setting
4: 4,800 baud
5: 9,600 baud
6: 19,200 baud
RS-232C
Set to the same baud rate as the PT
ASCII, 7 data bits, 2 stop bits
Even
1-to-N (see note)
Level 1
00
Set to 2.
Set both switches SW1 and SW2 to 0.