Specifications of DS6-34DSX134N0-N

Supply Voltage Range
24 VDC
No. Of Phases
Three
Power Rating
75kW
Current Rating
134A
Operating Temperature Range
0°C To +40°C
Horsepower, 3-phase
100hp
Features
Soft Start
Horsepower, 1-phase
40hp
Instructional Leafl et IL03901001E
Effective June 2009
Storage
It is recommended that the unit be stored in its original shipping
box/crate until it is to be installed.
The unit should be stored in a location where:
Mounting instructions
The DS6 solid-state soft start controller is easy to mount. It does not
require any special tools. To aid you with panel layout, refer to the
dimension drawings shown in Figure 1 and Figure 2. Drill and tap
holes per mounting hole/slot locations as shown. To mount the unit,
use all the hardware specified in Table 1 of this leaflet. Tighten to
the specified torque.
Figure 1. 25- to 75-Horsepower Models
Figure 2. 100- to 150-Horsepower Models
2
(22.5)
(15.0)
The ambient temperature is between –13°F to 140°F
(–25°C to 60°C)
The relative humidity is between 0% and 95%, noncondensing
The environment is dry, clean, and noncorrosive
The unit will not be subjected to high shock or
vibration conditions
0.86
0.59
PE
PE
(30.0)
(35.0)
1.18
1.38
(93.0)
3.66
(108.0)
4.25
(30.0)
1.18
(35.0)
1.38
EATON CORPORATION www.eaton.com
(15.0)
0.59
PE
PE
(129.0)
(22.5)
0.86
5.08
(158.0)
6.22
(161.0)
6.34
(200.0)
7.87
(215.0)
8.47
(175.0)
6.89
(52.5)
2.07
(35.0)
1.38
(178.0)
7.01
(139.0)
5.47
HAZARDOUS VOLTAGE CAN CAUSE ELECTRIC SHOCK AND BURNS. TO
AVOID SHOCK HAZARD, DISCONNECT ALL POWER TO THE CONTROLLER,
MOTOR, OR OTHER CONTROL DEVICES BEFORE ANY WORK IS PERFORMED
ON THIS EQUIPMENT. FAILURE TO DO SO WILL RESULT IN PERSONAL
INJURY, DEATH, OR SUBSTANTIAL PROPERTY DAMAGE.
DO NOT APPLY A DISCONNECT DEVICE ON THE OUTPUT OF THE DS6 SOFT
START CONTROLLER UNLESS A MEANS TO TURN OFF THE DEVICE WHEN
DISCONNECT SWITCH IS OPEN IS UTILIZED. OPENING THE DISCONNECT
WHILE THE SOFT START CONTROLLER IS OPERATING MAY CAUSE A MAL-
FUNCTION. CLOSING THE DISCONNECT SWITCH WHILE THE SOFT START
CONTROLLER IS OPERATING WILL RESULT IN POTENTIAL EQUIPMENT
DAMAGE AND PERSONNEL HAZARD.
Table 1. Mounting Hardware and Torque Specifications
Table 2. Environmental Requirements
Frame Size
25–75 hp
100–150 hp
Description
Operating temperature
Storage temperature
Elevation
Humidity
Operating orientation
Minimum clearance—
upper and lower
Minimum clearance—sides
Minimum clearance—face
Shock resistance
Vibration resistance
Environment
Emissions
Screw Size + Flat
and Lock Washer
5 mm x 55 mm
6 mm x 65 mm
DANGER—HIGH VOLTAGE
Requirements
32°F to 104°F (0°C to 40°C) up to 140°F (60°C) with derating
of 1% of rated current per Kelvin
–13°F to 140°F (–25°C to 60°C )
Up to 1000m; up to 2000m with derating of 1% rated current
for each 100m
Functional to 95% noncondensing.
Less than 30 degrees from horizontal
2.165 inches (55 mm) to a wall, 0.984 inches (25 mm) to a
NZM1 (size 1), 1.378 inches (35 mm) to a NZM2 (size 2), con-
sult documentation of the breaker used (ionization emissions)
0.0 inches (0 mm)
0.198 inches (5 mm)
8g for 11 ms in any direction.
2M2 EN 60721-3-2: 10g (3.5 mm amplitude, 9 to 200 Hz)
Suitable for installation in a pollution Degree 2 environment
The device is suitable for use in industrial environments in
accordance with EN 55011/22 Class A
DS6 series soft start controllers
Quantity
2
2
Torque
Requirements
80 lb-in (9 Nm)
123 lb-in (14 Nm)
Unit Weight
Lbs (kg)
4.0 (1.8)
8.2 (3.7)