DS6-34DSX134N0-N EATON CUTLER HAMMER, DS6-34DSX134N0-N Datasheet - Page 8

Motor Starter

DS6-34DSX134N0-N

Manufacturer Part Number
DS6-34DSX134N0-N
Description
Motor Starter
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of DS6-34DSX134N0-N

Supply Voltage Range
24 VDC
No. Of Phases
Three
Power Rating
75kW
Current Rating
134A
Operating Temperature Range
0°C To +40°C
Horsepower, 3-phase
100hp
Features
Soft Start
Horsepower, 1-phase
40hp
Instructional Leafl et IL03901001E
Effective June 2009
Service
For additional information on this product, please call Eaton’s
Technical Resource Center at (877) 386-2273 or visit our Web site
at www.eaton.com.
Service and repair is available from Eaton or several factory-
authorized regional service centers. Please contact Eaton’s Product
Integrity Center at (800) 345-0434 for the location nearest to you.
For field service or start-up assistance 24 hours a day, 7 days a
week, please call (800) 498-2678.
The following chart describes LED operation during motor start,
run, and stop conditions.
Eaton Corporation
Electrical Sector
1000 Cherrington Parkway
Moon Township, PA 15108
United States
877-ETN-CARE (877-386-2273)
Eaton.com
© 2009 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. IL03901001E / Z8490
June 2009
Table 10. LED Operation During Motor Start, Run, and
Stop Conditions
N
and STOP commands. If this is the case, a normal ramp start with a normal
stop (coast) will be selected.
When signaling a STOP command, either terminal may be de-energized. If
terminal +A1 is de-energized, a ramp stop will be selected. If terminal EN is
de-energized, a normal stop (coast) will be selected. To initiate another start,
simply re-energize the controlled (switched) terminal.
During ramp start or ramp stop, the RUN LED will be flashing—long pulse.
Condition
24 Vdc applied
and initialization
complete
Terminal EN
energized
Terminals EN and
+A1 energized
End of ramp time
Terminal +A1
de-energized
EN-energized
Terminal EN
de-energized
Error detected
otes:
Terminals EN and +A1 may be connected together to provide START
Motor Status
Off
Off
START
command—
motor rotation
At rated RPM
STOP
command—
ramp stop
STOP
command—
coast
Off
DS6 series soft start controllers
Ready
Contacts
Closed
Closed
Closed
Closed
Closed
Closed
Open
PowerChain Management is a registered
trademark of Eaton Corporation.
All other trademarks are property of their
respective owners.
TOR
Contacts
Open
Open
Open
Closed
Open
Open
Open
Error LED
Flashing—
short pulse
Off
Off
Off
Off
Flashing—
short pulse
Flashing—
long pulse
Run LED
Flashing—
short pulse
Flashing—
short pulse
Flashing—
long pulse
On
Flashing—
long pulse
Flashing—
short pulse
Off