DS6-34DSX134N0-N EATON CUTLER HAMMER, DS6-34DSX134N0-N Datasheet - Page 3

Motor Starter

DS6-34DSX134N0-N

Manufacturer Part Number
DS6-34DSX134N0-N
Description
Motor Starter
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of DS6-34DSX134N0-N

Supply Voltage Range
24 VDC
No. Of Phases
Three
Power Rating
75kW
Current Rating
134A
Operating Temperature Range
0°C To +40°C
Horsepower, 3-phase
100hp
Features
Soft Start
Horsepower, 1-phase
40hp
DS6 series soft start controllers
Power wiring
Using the wiring diagrams in Figure 3, Figure 4, and Table 3 as
guides, connect the line, motor, and power supply wiring in
accordance with appropriate local and national codes.
N
should be tightly bundled and run perpendicular to the orientation of the DS6.
Soft start controller to motor cable length is not to exceed 325 ft (100m).
Figure 3. Power Wiring Diagram for 230/400 and 400/460V
Line Voltages
Table 4. Product Selection—Horsepower Ratings
Table 5. Product Selection—kW Ratings According to IEC 60947-4-2
Considerations:
1. Either XTOB, C306, or C396 series or equivalent overload protection devices may be selected.
2. Isolation contactor is optional for normal applications. It is recommended for mains isolation.
Catalog Number
DS6-34DSX041N0-N
DS6-34DSX055N0-N
DS6-34DSX068N0-N
DS6-34DSX081N0-N
DS6-34DSX099N0-N
DS6-34DSX134N0-N
DS6-34DSX161N0-N
DS6-34DSX196N0-N
Catalog Number
DS6-34DSX041N0-N
DS6-34DSX055N0-N
DS6-34DSX068N0-N
DS6-34DSX081N0-N
DS6-34DSX099N0-N
DS6-34DSX134N0-N
DS6-34DSX161N0-N
DS6-34DSX196N0-N
ote:
Maximum values are higher than allowed per NEC 430.52 and UL 508A 31.1.
Maximum values are higher than allowed per NEC 430.52 and UL 508A 31.1.
To provide optimum motor protection, the line and motor power wiring
2
1
T1
L1
Rated
Current
(A)
40
52
65
77
96
124
156
180
Rated
Current
(A)
41
55
68
81
99
134
161
196
DS6
3
4
3~
M
T2
L2
5
6
T3
L3
Motor Power
200V
(hp)
10
15
20
25
30
40
50
60
Motor Power
230V
(kW)
11
15
15
22
30
30
45
55
230V
(hp)
10
20
25
30
30
50
60
75
400V
(kW)
22
30
37
45
55
75
90
110
460V
(hp)
30
40
50
60
75
100
125
150
Table 3. Power Wire Sizing and Torque Requirements
HAZARDOUS VOLTAGE. WILL CAUSE DEATH OR SERIOUS INJURY.
HAZARDOUS VOLTAGE IS PRESENT IN THE OFF/STOP STATUS OF THE SOFT
START CONTROLLER WHEN THE LINE VOLTAGE IS ENERGIZED.
Frame Size
25–75 hp
25–75 hp
100–150 hp
100–150 hp
Maximum Allowable
Breaker Size
HFD3150L
HFD3200L
HJD3250
HKD3300
HKD3350
HKD3350
HLD3450
HLD3500
Maximum Allowable
Breaker Size
HFD3150L
HFD3200L
HJD3250
HKD3300
HKD3350
HKD3350
HLD3450
HLD3500
Wire Size
12–8 AWG
6–2/0 AWG
12–8 AWG
6 AWG—350 kcmil
EATON CORPORATION www.eaton.com
Instructional Leafl et IL03901001E
DANGER
Torque
53 lb-in
80 lb-in
44 lb-in
123 lb-in
Maximum Allowable
Fuse Size
150A Class RK5
200A Class RK5
200A Class RK5
300A Class RK5
350A Class RK5
500A Class RK5
500A Class RK5
500A Class RK5
Maximum Allowable
Fuse Size
150A Class RK5
200A Class RK5
200A Class RK5
300A Class RK5
350A Class RK5
500A Class RK5
500A Class RK5
500A Class RK5
Effective June 2009
Wire Strip Length
0.65 in
0.65 in
0.87 in
0.87 in
3