DS6-34DSX134N0-N EATON CUTLER HAMMER, DS6-34DSX134N0-N Datasheet - Page 6

Motor Starter

DS6-34DSX134N0-N

Manufacturer Part Number
DS6-34DSX134N0-N
Description
Motor Starter
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of DS6-34DSX134N0-N

Supply Voltage Range
24 VDC
No. Of Phases
Three
Power Rating
75kW
Current Rating
134A
Operating Temperature Range
0°C To +40°C
Horsepower, 3-phase
100hp
Features
Soft Start
Horsepower, 1-phase
40hp
Instructional Leafl et IL03901001E
Effective June 2009
Table 8. DS6 Parameters
N
Applications with high starting torque are not suitable for DS6 soft start controllers. In some cases, over-sizing to a larger unit may be a solution.
Consult Eaton’s Technical Resource Center at (877) 386-2273.
6
Application
Axial-flow compressor
Bandsaw
Drill, unloaded
Crusher, empty at start
Carding machine (combing cotton)
Conveyor, horizontal, loaded
Conveyor, horizontal, unloaded
Conveyor, vertical, loaded
Conveyor, vertical, unloaded
Conveyor, vertical drop, loaded
Conveyor, vertical drop, unloaded
Crusher, swing hammer
Chiller
Piston compressor, unloaded
Circular saw
Ball mill
Flour mill
Mixer, liquids
Mixer, plastic materials
Mixer, powder materials
Mixer, dry materials
Pelletizing machine
Pump, piston
Pump, centrifugal
Moving pavement, unloaded
Escalator
Rotary compressor, unloaded
Agitator
Grinder, unloaded
Feed screw
Compressor, screw, unloaded
Press, flywheel
Drier, rotating
Blower, axial fan, flaps closed
Blower, axial fan, flaps open
Blower, centrifugal fan, valve closed
Blower, centrifugal fan, valve open
Vibroconveyor
Vibrating screen
Rolling mill
Washing machine
Centifuge
otes:
u-Start % values are voltage settings, as the starting torque is dependent on the application.
EATON CORPORATION www.eaton.com
t-Start
25s
10s
10s
20s
20s
25s
25s
25s
25s
25s
25s
25s
5s
10s
20s
20s
20s
10s
10s
10s
15s
20s
25s
10s
20s
10s
20s
15s
10s
20s
25s
25s
20s
40s
30s
40s
30s
25s
20s
25s
25s
60s
t-Stop
30s
30s
30s
30s
30s
30s
30s
30s
u-Start
48%
42%
29%
56%
64%
76%
48%
82%
59%
37%
44%
70%
37%
64%
48%
48%
44%
37%
70%
70%
56%
64%
82%
37%
37%
48%
42%
42%
37%
82%
40%
76%
64%
37%
37%
42%
35%
76%
51%
48%
64%
61%
Break-Away Torque
50%
35%
10%
75%
100%
150%
50%
175%
85%
25%
40%
125%
25%
100%
50%
50%
50%
40%
125%
125%
75%
100%
175%
25%
25%
50%
35%
35%
25%
175%
30%
150%
100%
25%
25%
35%
20%
150%
60%
100%
90%
DS6 series soft start controllers
Remarks
Possible high inertia
Eccentric load, high starting torque
Possible high inertia
Eccentric load
Possible high starting torque
Possible high starting torque
Possible high starting torque
Possible high inertia
Possible high starting torque
Possible high starting torque
Possible high starting torque
Possible high starting torque
High transmission ratio
High inertia, long ramp time

Related parts for DS6-34DSX134N0-N