6ED1 052-2CC00-0BA5 SIEMENS, 6ED1 052-2CC00-0BA5 Datasheet - Page 60

no-image

6ED1 052-2CC00-0BA5

Manufacturer Part Number
6ED1 052-2CC00-0BA5
Description
MODULE, LOGO!, 24O
Manufacturer
SIEMENS
Datasheet

Specifications of 6ED1 052-2CC00-0BA5

No. Of Analogue Inputs
2
No. Of Analogue Outputs
2
No. Of Digital Inputs
8
No. Of Digital Outputs
4
Ip/nema Rating
IP20
Approval Bodies
CSA, FM, IEC, UL, VDE
Approval Category
External Depth
4
Analog modules
SM 331 analog input modules
Technical specifications (continued)
Analog value formation
• Measuring principle
Integration and conversion time/
triggering per channel
Sensor
Sensing element connection
Error/accuracies
Operational limit in the entire
temperature range
- with over-range (bits incl. sign),
- Integration time parameterizable
- Basic conversion time, ms
- Interference voltage suppr. for
- for resistance measurement,
- for resistance measurement,
- for resistance measurement,
- relative to the input range,
- relative to the input range,
- relative to the input range,
4/32
max
interference frequency f1 in Hz
with 2-wire connection
with 3-wire connection
with 4-wire connection
voltage
resistance
resistance thermometer
SIMATIC S7-300
Siemens ST 70 News · 2006
6ES7 331-
7PF01-0AB0
integrating
16 Bit; Two’s
complement
Yes
up to 4 chan-
nels: 10 ms
per module,
as of 5 chan-
nels: 190 ms
per module,
8 channels: 80
ms
400 / 60 /
50 Hz
Yes; without
resistance
correction
Yes
Yes
+/- 0,1 %
+/- 1 K
6ES7 331-
7PF11-0AB0
integrating
16 Bit; Two’s
complement
Yes
up to 4 chan-
nels: 10 ms
per module,
as of 5 chan-
nels: 190 ms
per module
400 / 60 /
50 Hz
+/- 1 K
Basic error limit
(operational limit at 25 °C)
Status information/ interrupts/
diagnostics
Interrupts
Diagnostics
Insulation
• Insulation tested with
Potentials/ electrical isolation
Analog output functions
Dimensions and weight
• Weight, approx.
• Width
• Height
• Depth
- relative to the input range,
- relative to the input range,
- Diagnostic interrupt
- Limit value interrupt
- Diagnostic information can be
- between the channels
- between the channels,
- between the channels and the
resistance
resistance thermometer
read out
in groups of
backplane bus
6ES7 331-
7PF01-0AB0
+/- 0,05 %
+/- 0.5 K
Yes; parame-
terizable per
group
Yes; parame-
terizable
Yes
500 V DC
Yes
2
Yes
272 g
40 mm
125 mm
120 mm
6ES7 331-
7PF11-0AB0
Yes; parame-
terizable per
group
Yes; parame-
terizable
Yes
500 V DC
Yes
2
Yes
272 g
40 mm
125 mm
120 mm

Related parts for 6ED1 052-2CC00-0BA5