N8760A-861-208 AGILENT TECHNOLOGIES, N8760A-861-208 Datasheet - Page 12

POWER SUPPLY, DC, 150V, 5.1KW

N8760A-861-208

Manufacturer Part Number
N8760A-861-208
Description
POWER SUPPLY, DC, 150V, 5.1KW
Manufacturer
AGILENT TECHNOLOGIES
Datasheet

Specifications of N8760A-861-208

Power Supply Output Type
Programmable
No. Of Outputs
1
Output Voltage
150V
Output Current
34A
Power Rating
5100W
Input Voltage
170V AC To 265V AC
Length
442.5mm
Width
423mm
Height
88mm
Lead Free Status / RoHS Status
na
Supplemental Characteristics
Notes:
8. The constant current programming readback and monitoring accuracy does not include the warm-up and load regulation thermal drift.
Analog programming and monitoring
V
I
V
I
On/Off control (rear panel)
Output current monitor
Output voltage monitor
Power supply OK signal
CV/CC Indicator
Enable/disable
Series and parallel capability
Parallel operation
Series operation
Savable states
In volatile memory
Interface capabilities
GPIB
LXI Compliance
USB 2.0
10/100 LAN
Environmental conditions
Environment
Operating temperature
Storage temperature
Operating humidity
Storage humidity
Altitude
Built-in Web server
out
out
out
out
voltage programming
resistor programming
voltage programming
resistor programming
8
8
8
0-100%, 0-5 V or 0-10 V, user selectable. Accuracy and linearity: ±0.5% of rated V
0-100%, 0-5 V or 0-10 V, user selectable. Accuracy and linearity: ±1% of rated I
0-100%, 0-5/10 Kohm full scale, user selectable. Accuracy and linearity: ±1% of rated V
0-100%, 0-5/10 Kohm full scale, user selectable. Accuracy and linearity: ±1.5% of rated I
Controlled by voltage: 0-0.6 V/2-15 V, or dry contact, user selectable logic.
0-5 V or 0-10 V, user selectable, Accuracy: ±1%.
0-5 V or 0-10 V, user selectable, Accuracy: ±1%.
TTL high (4-5 V) = OK; 0 V = Fail; 500 ohm series resistance.
3.3 kW: CV = TTL high (4-5 V) (source current: 10 mA); CC = TTL low (0-0.6 V) (sink current = 10 mA)
5 kW: Open collector; CV mode: OFF, CC mode: ON, Max voltage = 30 V; Max sink current = 10 mA
Dry contact. Open: off, Short: on. Max. voltage at terminal = 6 V
Up to 4 identical units (same model number) can be connected in master/slave mode with
single-wire current balancing
Up to 2 identical units (same model number) can be connected using external protection diodes
(see Output Terminal Isolation on page 13)
16 (in memory locations 0-15)
SCPI - 1993, IEEE 488.2 compliant interface
Class C (only apples to units with the LXI label on the front panel)
Requires Agilent I/O Library version M.01.01 and up, or 14.0 and up
Requires Agilent I/O Library version L.01.01 and up, or 14.0 and up
Indoor use, installation category II (AC input), pollution degree 2
0°C to 40°C @ 100% load
–20°C to 70°C
30% to 90% relative humidity (no condensation)
10% to 95% relative humidity (no condensation)
Up to 3000 meters.
Above 2000 m, derate the output current by 2%/100 m and derate the maximum ambient
temperature by 1°C/100 m.
Requires Internet Explorer 5+ or Netscape 6.2+
All Models (unless otherwise specified)
(Continued)
12
out
out
.
.
out
out
.
.

Related parts for N8760A-861-208