C200H-TC001 Omron, C200H-TC001 Datasheet - Page 17

no-image

C200H-TC001

Manufacturer Part Number
C200H-TC001
Description
THERMOCOUPLE IN/ RELAY OUT
Manufacturer
Omron
Datasheet

Specifications of C200H-TC001

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
J System Configuration
Two tem-
perature
sensors
J Features
Supports 2-loop PID control (two degrees of freedom)
or ON/OFF control.
Input directly from two temperature sensors (thermo-
couples: R, S, K, J, T, E, B, N, L, or U) or platinum re-
sistance thermometers (JPt00, Pt100).
Open-collector, voltage, or current outputs.
Sampling period: 500 ms.
Run/start control.
Two internal alarms per loop.
Detects heater burnout through current detectors for
both loops.
Record up to eight sets of set points, alarm values and
PID parameters.
Connects to Data Setting Console.
C200H-TVjjj
MV
Heat
Output cable
Cool
C200H-DSC01
Data Setting Console
PV
MV
Manipulated variable
Heat
Data Setting
Console
Cool
PV
Perform 2--loop PID control (two degrees of freedom)
based on inputs from thermocouples or platinum resist-
ance thermometers to control a transistor, voltage or cur-
rent output. Words allocated to the Module in memory
can be manipulated from the ladder diagram to start/stop
operation, set the target value, read the process value, or
perform other operations.
Programmable Controller
Heat/Cool Control Module
Special I/O Modules
CS1
C--89

Related parts for C200H-TC001