CS1D-BC042D Omron, CS1D-BC042D Datasheet - Page 327

no-image

CS1D-BC042D

Manufacturer Part Number
CS1D-BC042D
Description
CS1D Dual CPU Exp
Manufacturer
Omron
Datasheet

Specifications of CS1D-BC042D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Debugging Information
292
Auxiliary Area
Online Editing Wait Flag
Online Editing Processing
Flag
Online Editing Disable Bit Vali-
dator
Online Editing Disable Bit
Output OFF Bit
Differentiate Monitor Com-
pleted Flag
Sampling Start Bit
Trace Start Bit
Trace Busy Flag
Trace Completed Flag
Trace Trigger Monitor Flag
Online Editing
Output Control
Differentiate Monitor
Data Tracing
Name
Name
Name
Name
A20110
A20111
A52700 to
A52707
A52709
A50015
A50809
A50815
A50814
A50813
A50812
A50811
Address
Address
Address
Address
ON when an online editing process is waiting.
(An online editing request was received while online editing
was disabled.)
ON when an online editing process is being executed.
The Online Editing Disable Bit (A52709) is valid only when
this byte contains 5A.
Turn this bit ON to disable online editing.
(A52700 to A52707 must be set to 5A.)
Turn this bit ON to turn OFF all outputs from Basic I/O Units,
Output Units, and Special I/O Units.
ON when the differentiate monitor condition has been estab-
lished during execution of differentiation monitoring.
When a data trace is started by turning this bit from OFF to
ON from a Programming Device, the PLC will begin storing
data in Trace Memory by one of the three following methods:
1) Periodic sampling (10 to 2,550 ms)
2) Sampling at execution of TRSM(045)
3) Sampling at the end of every cycle.
Turn this bit from OFF to ON to establish the trigger condi-
tion. The offset indicated by the delay value (positive or neg-
ative) determines which data samples are valid.
ON when the Sampling Start Bit (A50815) is turned from
OFF to ON. OFF when the trace is completed.
ON when sampling of a region of trace memory has been
completed during execution of a Trace. OFF when the next
time the Sampling Start Bit (A50815) is turned from OFF to
ON.
ON when a trigger condition is established by the Trace Start
Bit (A50814). OFF when the next Data Trace is started by
the Sampling Start bit (A50815).
Description
Description
Description
Description
Section 8-11
Read-only
Read-only
Read/write
Read/write
Read/write
Read/write
Read/write
Read/write
Read/write
Read/write
Read/write
Access
Access
Access
Access

Related parts for CS1D-BC042D