Online Replacement of I/O Units, Special I/O Units, and CPU Bus Units
Basic Procedure
Example Procedure
436
1,2,3...
Initial
display
Remove
Unit
1. Connect a Programming Console to the peripheral port on the active CPU
2. Access the I/O table creation display from the initial display by pressing the
3. Select online replacement by pressing the EXT Key.
4. Specify the number of the Rack and the slot where the Unit is to be re-
Rack
No.
Unit.
keys shown below.
To exit online replacement, go to step 7. To start online replacement, con-
tinue to step 4.
placed.
In this example, slot 8 on Rack 5 is used. In 5-8=I32 in the following dis-
plays, 5 is the rack number, 8 is the slot number, and I32 is the Unit type.
FUN
DEL
INS
EM_/EXT
Slot
No.
*EM
SHIFT
FUN
Mount
Unit
SRCH
SHIFT
CF
*DM
CH
EM_/EXT
SRCH
CLR
*DM
*EM
CH
CF
5
8
000000 I/O TBL ?
Replace?
Replace?
Replace?
Replace?
000000 CT**
1. Display the initial display
2. Select online
3. Specify the Rack and slot
4. Start the online
5. Replace the Unit.
6. Complete the online
?-?=
5-?=
5-8=
5-8=I32
for the I/O table creation
operation.
replacement.
of the Unit to be replaced.
replacement.
replacement operation.