CS1D-BC042D Omron, CS1D-BC042D Datasheet - Page 64

no-image

CS1D-BC042D

Manufacturer Part Number
CS1D-BC042D
Description
CS1D Dual CPU Exp
Manufacturer
Omron
Datasheet

Specifications of CS1D-BC042D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
2-1-4
Specifications
CS1D Power Supply Unit
Power supply voltage
Operating voltage range
Power consumption
Inrush current
Power supply output capacity
Power supply output terminal
RUN output
(See note 3.)
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Ambient operating temperature
Ambient operating humidity
Atmosphere
Ambient storage temperature
Grounding
Enclosure
General Specifications
Item
Contact configu-
ration
Switch capacity
100 to 120 V AC/200 to
240 V, 50/60 Hz
85 to 132 V AC/170 to
264 V
150 VA max.
100 to 120 V AC: 30 A
max. (cold start at normal
temperatures); 8 ms max.
200 to 240 V AC: 40 A
max. (cold start at normal
temperatures); 8 ms max.
(See note 1.)
5 V DC, 7 A (including the
CPU Unit power supply)
26 V DC, 1.3 A
Total: 35 W max.
Not provided.
SPST-NO
240 V AC, 2A (resistive
load)
120 V AC, 0.5 A (induction
load)
24 V DC, 2A (resistive
load)
24 V DC, 2 A (induction
load)
20 M min. (at 500 V DC)
between AC external and
GR terminals (See note 2.)
2,300 V AC 50/60 Hz for 1
min between AC external
and GR terminals (See
note 2.)
Leakage current: 10 mA
max.
1,000 V AC 50/60 Hz for 1
min between AC external
and GR terminals (See
note 2.)
Leakage current: 10 mA
max.
2 kV on power supply line (conforming to IEC61000-4-4)
10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s
directions for 80 minutes
(Time coefficient: 8 minutes
147 m/s
0 to 55 C
10% to 90% (with no condensation)
Must be free from corrosive gases.
Less than 100
Mounted in a panel.
20 to 75 C (excluding battery)
CS1D-PA207R
2
3 times each in X, Y, and Z directions (according to JIS 0041)
24 V DC
19.2 to 28.8 V DC
40 W max.
30 A max.
5 V DC, 4.3 A (including the
CPU Unit power supply)
26 V DC, 0.56 A
Total: 28 W max.
Not provided.
Not provided.
20 M min. (at 500 V DC)
between DC external and
GR terminals (See note 2.)
1,000 V AC 50/60 Hz for 1
min between DC external
and GR terminals (See note
2.)
Leakage current: 10 mA
max.
coefficient factor 10 = total time 80 min.)
Specifications
CS1D-PD024
24 V DC
19.2 to 28.8 V DC
60 W max.
30 A max.
5 V DC, 5.3 A (including the
CPU Unit power supply)
26 V DC, 1.3 A
Total: 40 W max.
Not provided.
Not provided.
20 M min. (at 500 V DC)
between DC external and
GR terminals (See note 2.)
1,000 V AC 50/60 Hz for 1
min between DC external
and GR terminals (See note
2.)
Leakage current: 10 mA
max.
CS1D-PD025
2
in X, Y, and Z
Section 2-1
29

Related parts for CS1D-BC042D